Specifications

32 www.amana-hac.com SS-AHKR
SS-AHKR www.amana-hac.com 33
Air Handler Electrical Data — MBVC
Models
Circuit 1 Circuit 2 Single-Point Kit
Heater Amps MCA¹ MOP² Heater Amps MCA¹ MOP² MCA¹ MOP²
MBVC1200AA-1A*
HKR-03*
HKR-05* / 05C*
HKR-06*
HKR-08* / -08C*
HKR-10* / -10C*
HKA-15C*
0 / 0
10.8 / 12.5
17.2 / 19.8
21.7 / 25.0
25.3 / 29.2
34.3 / 39.6
34.3 / 39.6
4.9 / 4.9
18 / 20.5
26 / 29.6
32 / 36.1
36.5 / 41
47.8 / 54
47.8 / 54
15 / 15
20 / 25
30 / 30
35 / 40
40 / 45
50 / 60
50 / 60
---
---
---
---
---
---
17.2 / 19.8
---
---
---
---
---
---
21.4 / 24.7
---
---
---
---
---
---
25 / 25
---
---
---
---
---
---
69/79
---
---
---
---
---
---
70 / 80
MBVC1600AA-1A*
HKR-03*
HKR-05* / 05C*
HKR-06*
HKR-08* / -08C*
HKR-10* / -10C*
HKA-15C*
0 / 0
10.8 / 12.5
17.2 / 19.8
21.7 / 25.0
25.3 / 29.2
34.3 / 39.6
34.3 / 39.6
6.5 / 6.5
20.1 / 22
27.9 / 31
34 / 37.8
38.1 / 43
49.4 / 56
49.4 / 56
15 / 15
25 / 25
30 / 35
35 / 40
40 / 45
50 / 60
50 / 60
---
---
---
---
---
---
17.2 / 19.8
---
---
---
---
---
---
21.4 / 24.7
---
---
---
---
---
---
25 / 25
---
---
---
---
---
---
71/81
---
---
---
---
---
---
80 / 90
MBVC2000AA-1A*
HKR-03*
HKR-05* / 05C*
HKR-06*
HKR-08* / -08C*
HKR-10* / -10C*
HKA-15C*
HKA-20C*
0 / 0
10.8 / 12.5
17.2 / 19.8
21.7 / 25.0
25.3 / 29.2
34.3 / 39.6
34.3 / 39.6
34.3 / 39.6
6.5 / 6.5
20.1 / 22
27.9 / 31
34 / 37.8
38.1 / 43
49.4 / 56
49.4 / 56
49.4 / 56
15 / 15
25 / 25
30 / 35
35 / 40
40 / 45
50 / 60
50 / 60
50 / 60
---
---
---
---
---
---
17.2 / 19.8
34.3 / 39.6
---
---
---
---
---
---
21.4 / 24.7
42.9 / 49.5
---
---
---
---
---
---
25 / 25
45 / 50
---
---
---
---
---
---
70/80
92/105
---
---
---
---
---
---
70 / 80
100 / 110
All ampacies noted above include air handler motor amps
Circuit 1: Single-phase for Air Handlers / Cir-
cuit 2: Three-phase for HKR3 Heater Kits
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protecon = 2.25 X Motor Amps + Heater Amps
* Revision level that may or may not be designated
C = Circuit Breaker Opon
--- indicates Not Required
Only applicable when HKA kits are included in table
HKA meets the new UL1995 requirements for 15 and 20KW heaters
MBVC and MBR models
Heating kW Correction Factor
Supply Voltage 240 230 220 210 208
Correction Factor 1.00 0.92 0.84 0.77 0.75
Mulply the 240-volt heang capacity by correcon factors.