GVZC20 Service Manual

TROUBLESHOOTING
97
Fault Code
Control Board
LED Display
Transmitted Climate
Talk Message
Thermostat Fault Probable Causes Corrective Actions
12 E12 OD CTRL FAIL1
Indicates a general memory error.
High electrical noise
Faulty control board
Replace control board if necessary
13 E13
HI PRESSURE C (C =
CRITICAL)
This error indicates the equipment
is experiencing frequent high
pressure faults.
Blocked/restricted condenser coil
and/or lines
Stop valve not completely open
Overcharge
Outdoor fan not running
High pressure switch (HPS)
inoperable
Faulty TXV
Faulty control board
Check and clean condenser coil and/or lines
Check the opening of stop valve, should be
full open; Repair/replace if needed
Check refrigerant charge level; Adjust if
needed
Check outdoor fan motor & wiring;
Repair/replace if needed
Check TXV; Replace if needed
Replace control board if necessary
14 -
HI PRESSURE M (M =
MINOR)
This error indicates the equipment
is experiencing frequent high
pressure faults. Control has
determined continued operation is
acceptable. This indicates they
may be a problem with the
equipment.
Blocked/restricted condenser coil
and/or lines
Stop valve not completely open
Overcharge
Outdoor fan not running
High pressure switch (HPS)
inoperable
Faulty TXV
Faulty control board
Check and clean condenser coil and/or lines
Check the opening of stop valve, should be
full open; Repair/replace if needed
Check refrigerant charge level; Adjust if
needed
Check outdoor fan motor & wiring;
Repair/replace if needed
Check TXV; Replace if needed
Replace control board if necessary
Check high pressure switch; Replace if
necessary
15 E15 LOW PRESSURE C
This error indicates the equipment
is experiencing frequent low
pressure faults.
Stop valve not completely open
Restriction in refrigerant lines
Low refrigerant charge
Refrigerant leak
Low pressure sensor inoperable or
not properly connected
Indoor fan motor not functioning
correctly
Faulty TXV
Faulty control board
Check the opening of stop valve, should be
full open; Repair/replace if needed
Check for restrictions in refrigerant line;
Repair/replace if needed
Check refrigerant charge level; Adjust if
needed
Test for system leaks using leak test
procedure
Check the connection to low pressure sensor;
Repair/replace if needed
Check TXV; Replace if needed
Check indoor blower motor & wiring;
Repair/replace if needed
Replace control board if necessary
16 - LOW PRESSURE M
This error indicates the equipment
is experiencing frequent low
pressure faults. Control has
determined continued operation is
acceptable. This indicates they
may be a problem with the
equipment.
Stop valve not completely open
Restriction in refrigerant lines
Low refrigerant charge
Refrigerant leak
Low pressure sensor inoperable or
not properly connected
Indoor fan motor not functioning
correctly
Faulty TXV
Faulty control board
Check the opening of stop valve, should be
full open; Repair/replace if needed
Check for restrictions in refrigerant line;
Repair/replace if needed
Check refrigerant charge level; Adjust if
needed
Test for system leaks using leak test
procedure
Check the connection to low pressure sensor;
Repair/replace if needed
Check TXV; Replace if needed
Check indoor blower motor & wiring;
Repair/replace if needed
Replace control board if necessary
17 E17 COMPRESSOR FAIL
This error indicates the equipment
is experiencing frequent
compressor faults.
Stop valve not completely open
The compressor wire is lost phase
Compressor motor failure
Check the opening of stop valve, should be
full open; Repair/replace if needed
Check the wire between control board and
compressor
Inspect compressor motor for proper function;
Replace if necessary
18 E18 OD CTRL FAIL2
Indicates the control board may
need to be replaced.
Outdoor fan motor not connected
properly
Faulty control board
Noise
Check wiring from Outdoor fan motor to
control board; Repair if needed.
Replace control board if necessary
19 E19 PCB OR FAN FAIL
This error indicates the equipment
is experiencing frequent outdoor
control board and/or motor faults.
Obstruction in fan rotation
Outdoor fan motor not connected
properly
Outdoor fan not running
Faulty control borad
Noise
Check and clean grille or any debris
Check wiring from Outdoor fan motor to
control board; Repair if needed
Check outdoor fan motor & wiring.
Repair/replace if needed
Replace control board if necessary
20 E20 EEV OPEN CKT
EEV coil is not connected.
Outdoor EEV coil is not connected.
Faulty outdoor EEV coil.
Check outdoor EEV coil connection.
Repair/replace as needed.
21 E21 EEV CTRL FAIL
This error indicates the equipment
is experiencing frequent low
discharge superheat faults.
Thermistors inoperable or improperly
connected
Faulty TXV
Faulty outdoor EEV coil
Faulty outdoor EEV
Over charge
Faulty pressure sensor
Faulty control board
Check the connection to thermistors;
Repair/replace if needed
Check TXV; Replace/repair if needed
Check outdoor EEV coil; Repair/replace if
needed
Check outdoor EEV; Replace/repair if needed
Check refrigerant charge level; Adjust if
needed
Check pressure sensor; Repair/replace if
needed
Replace control board if necessary
(*1) This message displayed when using the CTKO4 thermostat.
(*2) This specication of *VZC20**1 or earlier model are di󰀨erent from this specication. For details, see the service manual that matches the major revisoin of model name.