CTK04 ADDENDUM
DEHUMIDIFICATION SELECT*
When Dehumidication mode exists, the circulating fan out-
put is reduced, increasing system run time, over cooling the
evaporator coil and ultimately removing more humidity from
the structure than if only in cooling mode. The system can
have Dehumidication operation in setting “STD”, “A”, “B” or
“C” of “Dehumidication Select” based on dehumidication
demand. Setting “STD” allows for the widest compressor
operation range with lower CFM than Cooling mode.
In the Enhanced Dehumidication (setting A, B and C)
the indoor airow is lower than Standard Dehumidication
(STD). Setting “A” allows for the same compressor oper-
ation range in Dehumidication operation with lower CFM
than standard dehumidication (STD). Setting “B” limits
compressor operation range and keeps high dehumidica-
tion capacity. In setting “C” the system runs xed at 100%
compressor and airow. See Figure 1.
NOTE: In high humidity environments, sweating on supply
ducts, cased coils or air handler cabinets can become an
issue in Enhanced Dehumidication operation. It is strongly
recommended covering then with 2” berglass insulation for
these installations.
* The specication of *VZC200241AF, 0361AE, 0481AE
and 0601AE or earlier models are dierent from this
specication.
For details, see the Installation Manual or Service Manual
that matches the Major and Minor revision of model name.
CFM
Min
Compressor speed
Max
C
B
A
CFM control