GVZC20 Service Manual

SERVICING
63


SCREEN 3 (SETTING MODE 1)
Setting No. Contents Setting Installer/Serviceman Notes
1 Cool Airow Trim High
*1, *2
0: -15% 2: -5% 4: 5% 6: 15%
1: -10% 3: 0% 5: 10%
2 Cool Airow Trim Int 0: -15% 3: 0% 6: 15%
9: Full
*3
1: -10% 4: 5% 7: 20%
2: -5% 5: 10% 8: 30%
3 Cool Airow Trim Low 0: -15%
3: 0% 6: 15%
9: Full
*3
1: -10% 4: 5% 7: 20%
2: -5% 5: 10% 8: 30%
4 Cool Prole 0: A 1: B 2: C
3: D
5 Cool Fan ON Delay
0: 5sec. 1: 10sec. 2: 20sec. 3: 30sec.
6 Cool Fan OFF Delay
0: 30sec. 1: 60sec. 2: 90sec. 3: 120sec.
7 Dehumidication Select
*4
0: STD 2: A 4: C
1: OFF 3: B
8 Heat Airow Trim High
*1
0: -15% 2: -5% 4: 5% 6: 15%
1: -10% 3: 0% 5: 10%
9 Heat Airow Trim Int 0: -15% 2: -5% 4: 5% 6: 15%
1: -10%
3: 0% 5: 10%
10 Heat Airow Trim Low 0: -15% 2: -5% 4: 5% 6: 15%
1: -10%
3: 0% 5: 10%
11 Heat Fan ON Delay
0: 5sec. 1: 10sec. 2: 15sec.
12 Heat Fan OFF Delay
0: 30sec. 1: 50sec. 2: 70sec. 3: 90sec.
13
Airow Trim Oset
*1, *2
0: 0% 1: +2.5% Used for additional trim setting by adding
2.5% to basic airow trim setting. This
setting aects all trim settings except
+15% High (cooling or heating).
NOTE: Parameters as per factory setting are highlighted in bold and underlined.
*1 *VZC200601* with **VC960804C, **VM970804C and *MVC800804C combination trim more than 5% settings are invalid.
Trimmed up CFM makes miss matching error.
*2 Depending on the connected indoor unit, there are restrictions on the posive side Trim setting.
If you want to change the Cool Airflow Trim to positive side, be sure to confirm the Airflow Trim restrictions in the latest indoor unit installaon
manual. The latest manual can be obtained from the websitePartnerLink(InfoFinderPlus/Literature)”.
[PartnerLink URL]
hps://partnerlinkmarkeng.goodmanmfg.com/goodman/info-finder-plus
*3 The Inverter system uses lower compressor speed and lower indoor unit CFM to opmize system performance.
*4 Please refer to the page of "D
EHUMIDIFICATION SELECT" for details of this funcon.
To obtain 100% CFM for home circulaon, use full Trim seng instead of Int/Low speed.
This is recommended for applicaons with unusually cold return temperatures such as basements.
NOTE:
The specification of *VZC200241AF, 0361AE, 0481AE and 0601AE or earlier models are different from this
specification. For details, see the Installation Manual or Service Manual that matches the Major and Minor revision of
model name.
