GVZC20 Service Manual
SERVICING
63
SCREEN 3 (SETTING MODE 1)
Setting No. Contents Setting Installer/Serviceman Notes
1 Cool Airow Trim High
*1, *2
0: -15% 2: -5% 4: 5% 6: 15%
1: -10% 3: 0% 5: 10%
2 Cool Airow Trim Int 0: -15% 3: 0% 6: 15%
9: Full
*3
1: -10% 4: 5% 7: 20%
2: -5% 5: 10% 8: 30%
3 Cool Airow Trim Low 0: -15%
3: 0% 6: 15%
9: Full
*3
1: -10% 4: 5% 7: 20%
2: -5% 5: 10% 8: 30%
4 Cool Prole 0: A 1: B 2: C
3: D
5 Cool Fan ON Delay
0: 5sec. 1: 10sec. 2: 20sec. 3: 30sec.
6 Cool Fan OFF Delay
0: 30sec. 1: 60sec. 2: 90sec. 3: 120sec.
7 Dehumidication Select
*4
0: STD 2: A 4: C
1: OFF 3: B
8 Heat Airow Trim High
*1
0: -15% 2: -5% 4: 5% 6: 15%
1: -10% 3: 0% 5: 10%
9 Heat Airow Trim Int 0: -15% 2: -5% 4: 5% 6: 15%
1: -10%
3: 0% 5: 10%
10 Heat Airow Trim Low 0: -15% 2: -5% 4: 5% 6: 15%
1: -10%
3: 0% 5: 10%
11 Heat Fan ON Delay
0: 5sec. 1: 10sec. 2: 15sec.
12 Heat Fan OFF Delay
0: 30sec. 1: 50sec. 2: 70sec. 3: 90sec.
13
Airow Trim Oset
*1, *2
0: 0% 1: +2.5% Used for additional trim setting by adding
2.5% to basic airow trim setting. This
setting aects all trim settings except
+15% High (cooling or heating).
NOTE: Parameters as per factory setting are highlighted in bold and underlined.
*1 *VZC200601* with **VC960804C, **VM970804C and *MVC800804C combination trim more than 5% settings are invalid.
Trimmed up CFM makes miss matching error.
*2 Depending on the connected indoor unit, there are restrictions on the posive side Trim setting.
If you want to change the Cool Airflow Trim to positive side, be sure to confirm the Airflow Trim restrictions in the latest indoor unit installaon
manual. The latest manual can be obtained from the website “PartnerLink(InfoFinderPlus/Literature)”.
[PartnerLink URL]
hps://partnerlinkmarkeng.goodmanmfg.com/goodman/info-finder-plus
*3 The Inverter system uses lower compressor speed and lower indoor unit CFM to opmize system performance.
*4 Please refer to the page of "D
EHUMIDIFICATION SELECT" for details of this funcon.
To obtain 100% CFM for home circulaon, use full Trim seng instead of Int/Low speed.
This is recommended for applicaons with unusually cold return temperatures such as basements.
NOTE:
The specification of *VZC200241AF, 0361AE, 0481AE and 0601AE or earlier models are different from this
specification. For details, see the Installation Manual or Service Manual that matches the Major and Minor revision of
model name.