GVZC20 Service Manual
SERVICING
32
COMMUNICATING BOARD
INDOOR UNIT TROUBLESHOOTING FOR TXV APPLICABLE UNIT (MBVC**00AA-1)
AUXILIARY ALARM SWITCH
The control is equipped with two Auxiliary Alarm terminals,
labeled CAS, which are typically utilized in series with a
condensate switch but could also be used with compatible
CO2 sensors or re alarms.
This feature can be activated or deactivated through the
thermostat user menus. The auxiliary alarm switch must be
normally closed and open when the alarm occurs. For ex-
ample, a normally closed condensate switch will open when
the base pan’s water level reaches a particular level. The
control will respond by turning o the blower motor and out-
door unit and displaying the proper fault codes. If the switch
is later detected closed for 30 seconds, normal operation
resumes and the error message is removed. The error will
be maintained in the equipment’s fault history. See FIGURE
15 on the following page for the connection location.
CIRCULATOR BLOWER
This air handler is equipped with a variable speed circulator
blower. This blower provides several automatically-adjusted
blower speeds. The Specication Sheet applicable to your
model provides an airow table, showing the relationship
between airow (CFM) and external static pressure (E.S.P.).
The electric heat dip switch default position is set to the
OFF, OFF, OFF position and should be adjusted by the in-
staller to match the installation requirements for the correct
electric heating CFM.
Using the Electric Heat Airow table below, set dip switch-
es 9, 10, and 11 for the installed heater kit. Verify selected
CFM by counting the green CFM LED blinks. The green
CFM LED blinks once for each 100 CFM of airow.
If an electric heater kit has not been installed, set dip
switches 9, 10, and 11 to any appropriate heater kit setting
(see next page table for valid settings).
During the cooling operation, the outdoor unit will determine
the indoor airow.










