GVZC20 Installation Manual
51
9. Once satisfied with BOOST MODE adjustments,
navigate to the HOME screen by selecting the Previous
Menu button three times then selecting HOME.
Dehumidification
The thermostat reads the indoor humidity level from the
CTK04 and allows the user to set a dehumidication target
based on these settings. The thermostat controls the
humidity level of the conditioned space using the cooling
system. Dehumidication is engaged whenever a cooling
demand is present and structural humidity levels are above
the target level. When this condition exists, the circulating
fan output is reduced, increasing system run time, over
cooling the evaporator coil and ultimately removing more
humidity from the structure than if only in cooling mode.
The CTK04 also allows for an additional overcooling limit
setting from 0°F to 3°F setup through the Installer Option
menu (directions following). This allows the cooling system
to further reduce humidity by lowering the temperature up
to 3°F below the cooling setpoint in an attempt to better
achieve desired humidity levels.
By default, dehumidication needs to be turned ON at the
thermostat via the Dehumidication Equipment menu. De-
humidication can be activated at the original equipment
setup by selecting the A/C with Low Speed Fan button in
the Dehumidication Menu. Availability can be veried by
pressing MENU on the home screen. Scroll down and if a De-
humidication button is present, dehumidication is activated.
If Dehumidication is not available in the menu then it must
be enabled through the Installer Options menu. Use the
following procedure to enable and disable dehumidication:
1. On the CTK04 HOME screen select MENU.
2. From the MENU screen, scroll down and select Installer
Options.
3. Enter installer password if known.
a. The password is the thermostat date code and can
be obtained by selecting the red Cancel button and
selecting the Dealer Information button.
b. Once recorded, click the green OK button and
return to the previous step.
4. Select YES to continue.
5. Select View / Edit Current Setup.
6. Scroll down and select Dehumidication.
7. Once open select Dehumidication Equipment: None.
8. From the Dehumidication Menu select A/C with Low
Speed Fan and click the green Done button.
9. Additional Dehumidication operational options can be
selected in the resulting window.
10. Once satised with the selection, navigate to the HOME
screen by selecting the Done button and selecting Yes
to verify the changes.
11. Select Previous Menu, then the HOME to return to the
main menu.
Dehumidification Tips
For eective dehumidication operation:
• Ensure “Dehum” is NOT set to “OFF” through the
Installer Options menu and/or in the ComfortNet User
Menu (COOL SETUP).
- If except OFF, the Dehumidication menu should
be visible in the main menu.
• Verify the cooling airow prole is set to “Prole D”.
• See the Cool Set-up section of the Installation
Manual for complete airow prole details.
• By default, “Dehum” is STD and the cooling airow
prole is set to “Prole D”.
• For additional dehumidication control, airow settings
are eld adjustable and can be ne-tuned to a value
that is comfortable for the application from a range of
Cool Airow Trim.
- In addition, the system can have Enhanced
Dehumidication operation in setting “A”, “B”,
or “C” of “Dehum” based on dehumidication
demand.
See the “Dehumidication Select” section of the
Installation Manual for more detail.