GVZC20 Installation Manual

18

A representative menu is posted. Item names and setting value are subject to change.
*1 At Cool and Heat Hi speed trim, *VZC200601* with **VC960804C,
**VM970804C and *MVC800804C combination trim more than 5% settings are invalid. Trimmed up CFM makes miss matching error.
*2 Other than the above, depending on the connected indoor unit, there are restrictions on the positive side Trim setting.
If you want to change the Cool Airow Trim to positive side, be sure to conrm the Airow Trim restrictions in the latest indoor unit installation manual.
The latest manual can be obtained from the website “PartnerLink(InfoFinderPlus/Literature)”.
[PartnerLink URL]
https://partnerlinkmarketing.goodmanmfg.com/goodman/info-nder-plus
*3 The Inverter system uses lower compressor speed and lower indoor unit CFM to optimize system performance.
To obtain 100% CFM for home circulation, use full Trim setting instead of Int/Low speed.
This is recommended for applications with unusually cold return temperatures such as basements.
*4 Please refer to the page of “DEHUMIDIFICATION SELECT “ for details of this function.
SUBMENU ITEM INDICATION(Units) COMMENTS
DEHUMIDIFICATION ENABLE
*4
Standard, OFF, A, B or C
Selecting "OFF" disables dehumidification
selecting.
"Standard", "A", "B" or "C" enables dehumidification.
RESET COOLING SETTINGS NO or YES
Selecting yes will reset any cooling setting to their
factory defaults.
RPS RANGE FOR COOLING
**.* to **.* RPS,…(Total 5 Ranges)
When determining the appropriate compressor
speed for cooling, select the range that contains the
desired value.
The Selected RPS for Cooling menu is where you
will select your desired value within this selected
range.
SELECTED RPS FOR COOLING **.* RPS
This value will be a number inside the RPS Range
for Cooling.
If you'd like to select a RPS from a different range,
you must change the RPS Range for Cooling
setting first, then restart the device setting page.
FORCE UNIT TO DEFROST MODE OFF or ON
Force the unit to run a defrost cycle.
Only available for inverter units.
This option only puts the compressor into defrost
mode during an active heat pump heat call.
Ensure that the heat pump is operating in heat
mode before enabling this option.
HEAT PUMP HEATING TRIM FACTOR (HIGH)
*1
-15% to +15% in 5% increments
Select this airflow trim when inverter system is
running high compressor speeds during a heating
cycle.
HEAT PUMP HEATING TRIM FACTOR (MID) -15% to +15% in 5% increments
Select this airflow trim when inverter system is
running mid-range (intermediate) compressor
speeds during a heating cycle.
HEAT PUMP HEATING TRIM FACTOR (LOW) -15% to +15% in 5% increments
Select this airflow trim when inverter system is
running low compressor speeds during a heating
cycle.
BLOWER ON DELAY-HEAT PUMP HEAT 5, 10 or15 Seconds
Delay between compressor turning on and indoor
blower turning on during a heating cycle.
BLOWER OFF DELAY-HEAT PUMP HEAT 30, 50, 70 or 90 Seconds
Delay between compressor shutting off and the
indoor blower shutting off after a heating cycle.
MAX ALLOW ED DEFROST INTERVAL 30, 60, 90, 120 Minutes
Select initial maximum amount of time allowed
between defrost cycles.
System will automatically determine next interval
refer to previous value (starting from this value)
after defrost operation.
RESET HEAT PUMP SETTINGS NO or YES
Selecting yes will reset any heat pump setting to
their factory defaults.
RPS RANGE FOR HEATING
**.* to **.* RPS,…(Total 5 Ranges)
When determining the appropriate compressor
speed for heating, select the range that contains
the desired value.
The Selected RPS for Heating menu is where you
will select your desired value within this selected
range.
SELECTED RPS FOR HEATING **.* RPS
This value will be a number inside the RPS Range
for Heating.
If you'd like to select a RPS from a different range,
you must change the RPS Range for Heating
setting first, then restart the device setting page.
RESET FAULT HISTORY NO or YES Selecting yes will clear the fault histories of device.
SUBMENU ITEM INDICATION(Units) COMMENTS
COMPRESSOR HEAT LOCKOUT 0F to 60F in 5F increments
The compressor will enter a lockout condition and
will not run while the outdoor ambient tenperature is
below the Compressor Heat Lockout temperature.
In this case, the system will use only the backup
heat source.

