TROUBLESHOOTING INFORMATION: UNITARY DIAGNOSTIC CODES
Digit3 Digit2 Digit 1
In
tegrated control module
diagnostic/status LED display shows
the indicated code.
BLANK A 2 • Outdoor air temp
sensor fault
Shorted sensor.
• Open sensor.
Sensor disconnected.
Sensor out of range.
• Check sensor
connection.
Replace open/ shorted
sensor.
T
urn power OFF prior to repair.
R
eplace with correct
replacement part.
• Heat pump fails to operate in
heating mode.
In
tegrated control module
diagnostic/status LED display shows
the indicated code.
BLANK A 3 Outdoor coil temp
sensor fault
Shorted sensor
• Open sensor.
Sensor. disconnected.
Sensor out of range.
• Check sensor
connection.
Re
place open/ shorted
sensor.
T
urn power OFF prior to repair.
R
eplace with correct
replacement part.
A
ir conditioner/heat pump fails to
operate.
In
tegrated control module
diagnostic/status LED display shows
the
indicated code.
BLANK E 5 Open fuse • Short in low voltage
wiring.
• Locate and correct short
in low voltage wiring.
• Turn power OFF prior to repair.
R
eplace fuse with
3-amp automotive type.
A
ir conditioner/heat pump fails to
operate.
In
tegrated control module
diagnostic/status LED display shows
the
indicated code.
BLANK E E Board mis- operation • Compressor relay
contacts welded.
R
eplace control. • Turn power OFF prior to repair
R
eplace with correct
replacement part.
A
ir conditioner/heat pump fails to
operate.
In
tegrated control module
diagnostic/status LED display shows
the indicated code.
BLANK b0 Circulator
blower motor is not
running when it
should be running.
In
door bIower motor
problem.
• Communications erro
r
be
tween indoor and
outdoor unit.
• Check indoor bIower
motor.
• Check indoor bIower
motor wiring.
Check indoor unit
control.
Re
pair/ replace any
faulty wiring.
R
epair/ replace
indoor bIower motor or
control.
T
urn power OFF prior to repair.
R
eplace with correct
replacement part.
A
ir conditioner/heat
pump operates at reduced
performance.
A
ir conditioner/heat pump
operating at low stage when expected
to operate at high stage.
In
tegrated control module
diagnostic/status LED display shows
the indicated code.
BLANK b9 Air flow is lower
than demanded
In
door bIower motor
problem
Bl
ocked filters .
R
estrictive/ undersized
ductwork
I
ndoor/ outdoor unit
miss-match.
• Check indoor blower
motor.
• Check Filters
clean/replace as needed.
• Check ductwork, resize
as needed.
V
erify indoor and
outdoor units are
p
roperly matched.
T
urn power OFF prior to repair.
R
eplace with correct
replacement part. See
specification sheets for airflo
w
r
equirements and maximu
m
ex
ternal static pressure.
• See specification sheets for
approved system matches.
SYSTEM TROUBLESHOOTING
UNITARY DIAGNOSTIC CODES
Symptoms of Abnormal
Operation
(Legacy & ComfortNet
Thermostat)
Diagnostic/Status LED
Display Codes
Fault Description Possible Causes
Corrective
Actions
Notes &
Cautions