TROUBLESHOOTING INFORMATION: UNITARY DIAGNOSTIC CODES
Digit 3 Digit 2 Digit 1
Air conditioner/heat pump
may appear to be operating
normally.
Compressor protecor may be
open (compressor and outdoor
fan off).
Integrated control module
diagnostic/status LED display
shows the indicated code.
BLANK H 8
High Line Voltage High line voltage
Correct high line
voltage condition;
contact local utility if
needed.
Verify unit is
connected to power
supply as specified on
rating plate.
Turn power OFF prior
to repair.
Control detects line
voltage greater than 255
VAC.
Fault will clear if line
voltage decreases
below 255 VAC.
Air conditioner/heat pump
may appear to be operating
normally.
Integrated control module
diagnostic/status LED display
shows the indicated code.
BLANK 0 9
Low Pilot Voltage
Control detects
secondary voltage
less than 18 VAC.
Transformer
overloaded.
Low line voltage.
Check fuse.
Correct low secondary
voltage condition.
Check transformer;
replace if needed.
Turn power OFF prior
to repair.
Fault will clear if
secondary voltage rises
above 21 VAC.
Replace with correct
replacement part(s).
Compressor is off.
Integrated control module
diagnostic/status LED display
shows the indicated code.
BLANK P 0
Comp protector
Open
No current through
run or start windings.
Compressor run
winding is open.
Compressor not
properly wired to
control.
Faulty Compressor
wiring.
Failed compressor
run capacitor.
Faulty run capacitor
wiring.
Check compressor;
repair/replace as
needed.
Check wiring
repair/replaced as
needed.
Check run capacitor;
replace as needed.
Turn power OFF prior
to repair.
Fault will clear after 1
normal cycle.
Must clear fault by
cycling 24 VAC to
control.
Replace with correct
replacement part(s).
Air conditioner/heat pump
may appear to be operating
normally.
Compressor protecor may be
open (compressor and outdoor
fan off).
Integrated control module
diagnostic/status LED display
shows the indicated code.
BLANK L 8
Low Line Voltage Low line voltage.
Check circuit
breakers and fuses.
Verify unit is
connected to power
supply as specified on
rating plate.
Correct low line
voltage condition;
contact local utility if
needed.
Turn power OFF prior
to repair.
Control detects line
voltage less than 1 85
VAC.
Fault will clear if line
voltage increases above
1 85 VAC.
Air conditioner/heat pump
may appear to be operating
normally.
Compressor protecor may be
open (compressor and outdoor
fan off).
Integrated control module
diagnostic/status LED display
shows the indicated code.
BLANK L 8
No Line Voltage • No line voltage.
Check circuit
breakers and fuses.
Verify unit is
connected to power
supply as specified on
rating plate.
Turn power OFF prior
to repair.
Control detects line
voltage less than 1 85
VAC.
Fault will clear if line
voltage increases above
1 85 VAC.
UNIT ARY DIAGNOST IC CODES
Symptoms of Abnormal
Operation
Diagnostic/Status
LED Display Codes
Fault Description Possible Causes Corrective Actions
Notes &
Cautions