GSZC16 Specs
Table Of Contents
Product Specifications
2 www.goodmanmfg.com SS-GSZC16
SS-GSZC16 www.goodmanmfg.com 3
GSZC16
0241C
GSZC16
0361C
GSZC16
0481C
GSZC16
0601C
Nominal Cooling (BTU/h) 24,000 36,000 48,000 60,000
Nominal Heang (BTU/h) 24,000 36,000 48,000 60,000
Decibels 73 73 75 75
RLA 10.0 14.8 20.4 22.9
LRA 62.9 84.2 122.1 147.2
Horsepower 1/5 1/5 1/5 1/3
FLA 1.0 1.0 1.0 2.8
Refrigerant Line Size¹
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ¾" ⅞" 1⅛” 1⅛”
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ¾" ⅞" ⅞" ⅞"
Valve Connecon Type Sweat Sweat Sweat Sweat
Refrigerant Charge (oz.) 176 170 244 288
Shipped with Orice Size NA NA NA NA
Volts -Hz 208/230-60 208/230-60 208/230-60 208/230-60
Minimum Circuit Ampacity ² 13.5 19.5 26.5 31.4
Max. Overcurrent Protecon ³ 20 30 45 50
Min / Max Volts 197/253 197/253 197/253 197/253
Power Supply Conduit Size ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"
Equipment Weight
215 240 291 313
Ship Weight (lbs)
240 266 316 339
^ Proper sizing and installaon of equipment is crical to achieve opmal performance. Split system air condioners and heat
pumps must be matched with appropriate coil components to meet ENERGY STAR® criteria. Ask your contractor for details or visit
www.energystar.gov. The www.energystar.gov website provides up-to-date system combinaons cered to meet ENERGY STAR
requirements. See Page 22 for all ENERGY STAR-cered combinaons as of this document’s revision date.
¹ Tested and rated in accordance with AHRI Standard 210/240
² Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
• Always check the rang plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge
Procedure.
• Installaon of these units requires the specied TXV Kit to be installed on the indoor coil.
THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT, NOT THE INDOOR COIL.