Installation Manual

5
REFRIGERANT UNDER PRESSURE!
F
AILURE
TO
FOLLOW
PROPER
PROCEDURES
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
.
WARNING
NOTE: Scroll compressors should never be used to evacuate
or pump down a heat pump or air conditioning system.
P
ROLONGED
OPERATION
AT
SUCTION
PRESSURES
LESS
THAN
20
PSIG
FOR
MORE
THAN
5
SECONDS
WILL
RESULT
IN
OVERHEATING
OF
THE
SCROLLS
AND
PERMANENT
DAMAGE
TO
THE
SCROLL
TIPS
,
DRIVE
BEARINGS
AND
INTERNAL
SEAL
.
CAUTION
1. Connect the vacuum pump with 250 micron capability
to the service valves.
2. Evacuate the system to 250 microns or less using
suction and liquid service valves. Using both valves is
necessary as some compressors create a mechanical
seal separating the sides of the system.
3. Close pump valve and hold vacuum for 10 minutes.
Typically pressure will rise during this period.
If the pressure rises to 1000 microns or less and
remains steady the system is considered leak-free;
proceed to startup.
If pressure rises above 1000 microns but holds
steady below 2000 microns, moisture and/or
noncondensibles may be present or the system may
have a small leak. Return to step 2: If the same
result is encountered check for leaks as previously
indicated and repair as necessary then repeat
evacuation.
If pressure rises above 2000 microns, a leak is
present. Check for leaks as previously indicated and
repair as necessary then repeat evacuation.
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0 1 2 3 4 5 6 7 8 9
10
LEAK(S)
PRESENT
MINUTES
V
ACUUM
IN
MICRONS
CONDENSIBLES OR SMALL
LEAK PRESENT
NO LEAKS
NO CONDENSIBLES
electrIcal connectIonS
HIGH VOLTAGE!
D
ISCONNECT
ALL
POWER
BEFORE
SERVICING
.
M
ULTIPLE
POWER
SOURCES
MAY
BE
PRESENT
. F
AILURE
TO
DO
SO
MAY
CAUSE
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
DUE
TO
ELECTRIC
SHOCK
. W
IRING
MUST
CONFORM
WITH
NEC
OR
CEC
AND
ALL
LOCAL
CODES
. U
NDERSIZED
WIRES
COULD
CAUSE
POOR
EQUIPMENT
PERFORMANCE
,
EQUIPMENT
DAMAGE
OR
FIRE
.
WARNING
T
O
AVOID
THE
RISK
OF
FIRE
OR
EQUIPMENT
DAMAGE
,
USE
COPPER
CONDUCTORS
.
WARNING
The condensing unit rating plate lists pertinent electrical
data necessary for proper electrical service and overcurrent
protection. Wires should be sized to limit voltage drop to 2%
(max.) from the main breaker or fuse panel to the condensing
unit. Consult the NEC, CEC, and all local codes to determine
the correct wire gauge and length.
Local codes often require a disconnect switch located near
the unit; do not install the switch on the unit. Refer to the
installation instructions supplied with the indoor furnace/air
handler for specic wiring connections and indoor unit con-
guration. Likewise, consult the instructions packaged with
the thermostat for mounting and location information.
overcurrent protectIon
The following overcurrent protection devices are approved
for use.
Time delay fuses
HACR type circuit breakers
These devices have sufcient time delay to permit the mo-
tor-compressor to start and accelerate its load.
hIgh voltage connectIonS
Route power supply and ground wires through the high volt-
age port and terminate in accordance with the wiring diagram
provided inside the control panel cover.
low voltage connectIonS
This heat pump is equipped with a factory-installed transformer
to power the outdoor controls when installed as part of a fully
communicating HVAC system utilizing a ComfortBridge
compatible indoor unit. In this conguration, only two low
voltage control wires are required between the outdoor unit
and indoor unit.
The unit also has legacy 24 VAC inputs and outputs to support
non-communicating systems. When this conguration is used,
the transformer in the outdoor unit must be disconnected from
the low voltage and line voltage connections. The transformer
connecting wires can then be discarded. Route control wires
through the low voltage port and terminate in accordance with
the wiring diagram provided inside the control panel cover.