GSZ16 Service Manual

67
ACCESSORIES
AVPTC**14**
Heat Kit Applications
TYPE/MODEL 24B14-A* 30C14-A* 36C14-A* 42C14-A* 48C14-A* 42D14-A* 48D14-A* 60D14-A*
HKSX03XC* X X X X X X X X
HKSX05XC* X X X X X X X X
HKSX06XC* X X X X X X X X
HKSX08XC* X X X X X X X X
HKSX10XC* X X X X X X X X
HKSX15XF* X X X X X X
HKSX20XF* X X X X X X
HKSC05XC* X X X X X X X X
HKSC08XC* X X X X X X X X
HKSC10XC* X X X X X X X X
HKSC15XA* X X X X X X
HKSC15XB* X X X X X X
HKSC15XF* X X X X X X
HKSC19CA* X X X
HKSC19CB* X X X
HKSC20DA* XXX
HKSC20DB* XXX
HKSC20XF* X X X X X X
HKSC25DC* XX
* Revision level that may or may not be designated.
Refer to the minimum airflow requirements for each of the heat kits.
ASPT
3 5 6 8 10 15 19 20 21 or 25
AVPTC24B14 550 650 700 800 850 NR NR NR NR
AVPTC30C14 600 700 750 875 950 NR NR NR NR
AVPTC36C14 NR 850 900 1000 1200 1440 1500 1500 NR
AVPTC48C14 NR 850 900 1000 1200 1440 1500 1500 NR
AVPTC 4 2 D 1 4
850** 1250 1300 1500 1550 1720 NR 1800 NR
AVPTC 4 8 D 1 4
††
NR 1250 1300 1500 1550 1720 NR 1815 1850
AVPTC 6 0 D 1 4
†††
NR 1250 1300 1500 1550 1780 NR 1850 1850
MINIMUM CFM REQUIRED FOR HEATER KITS, See notes below
†For match up w ith a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW.
Airflow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of ON-ON-ON.
††For match up w ith a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW.
Airflow for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
†††For match up w ith a 3.5 ton outdoor unit: Heater kit application shall not exceed 20 kW.
Airflow for 5 kW up to 20 kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF
** 3 kW heater kit is not applicable for this indoor application.
Note: Airflow data show n applies to the electric heat only in either legacy mode or communicating mode operation
NR - Not r ated
* Within thermostat user menu CTK0* communicating thermostat w ill display 20KW f or OFF- OFF- ON dip sw itch selection, 21kW for
Heater Kit (kW)