Specifications
Table Of Contents
2 www.goodmanmfg.com SS-GSZ16
SS-GSZ16 www.goodmanmfg.com 3
Product Specifications
GSZ16
0181B*
GSZ16
0241B*
GSZ16
0301B*
GSZ16
0361B*
GSZ16
0421B*
GSZ16
0481B*
GSZ16
0601B*
Cooling (BTU/h) 18,000 24,000 30,000 36,000 42,000 48,000 60,000
Heang (BTU/h) 18,000 24,000 30,000 36,000 42,000 48,000 60,000
Decibels 72 75 75 73 73 74 76
RLA 9.0 10.9 13.4 14.1 16.7 19.9 28.8
LRA 47.5 62.9 72.5 72.2 109.0 109.0 152.9
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Horsepower 1/6 1/6 1/6 1/4 1/4 1/4 1/6
FLA 0.95 1.1 1.1 1.30 1.2 1.30 1
Refrigerant Line Size¹
Liquid Line Size (“O.D.) 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
Sucon Line Size (“O.D.) 3/4" 3/4" 3/4" 7/8" 1 1/8" 1 1/8" 1 1/8"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
Sucon Valve Size (“O.D.) 3/4" 3/4" 7/8” 7/8" 7/8” 7/8" 7/8"
Valve Connecon Type Sweat Sweat Sweat Sweat Sweat Sweat Sweat
Refrigerant Charge (oz.) 140 150 160 175 180 231 291
Volts/Phase (60 Hz) 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Minimum Circuit Ampacity ² 12.2 14.7 18.0 18.9 22.1 26.2 37
Max. Overcurrent Protecon ³ 20 25 30 30 35 45 60
Min / Max Volts 197/253 197/253 197/253 197/253 197/253 197/253 197/253
Electrical Conduit Size 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4"
Equipment Weight 174 180 186 220 226 250 306
Shipping Weight 189 200 206 240 237 270 326
NO
Proper sizing and installaon of equipment is crical to achieving opmal performance. Split system air condioners and heat pumps must
be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your contractor for details or visit www.energystar.gov.
The www.energystar.gov website provides up-to-date system combinaons cered to meet ENERGY STAR requirements. See Page 21 for all ENERGY STAR cered combinaons
as of this document’s revision date.
¹ Tested and rated in accordance with AHRI Standard 210/240
² Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
• Always check the S&R plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.
• Installaon of these units requires the specied TXV Kit to be installed on the indoor coil.
THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.