Specifications

2 www.goodmanmfg.com SS-GSZ16
SS-GSZ16 www.goodmanmfg.com 3
Product Specifications
GSZ16
0181B*
GSZ16
0241B*
GSZ16
0301B*
GSZ16
0361B*
GSZ16
0421B*
GSZ16
0481B*
GSZ16
0601B*

Cooling (BTU/h) 18,000 24,000 30,000 36,000 42,000 48,000 60,000
Heang (BTU/h) 18,000 24,000 30,000 36,000 42,000 48,000 60,000
Decibels 72 75 75 73 73 74 76

RLA 9.0 10.9 13.4 14.1 16.7 19.9 28.8
LRA 47.5 62.9 72.5 72.2 109.0 109.0 152.9
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll

Horsepower 1/6 1/6 1/6 1/4 1/4 1/4 1/6
FLA 0.95 1.1 1.1 1.30 1.2 1.30 1

Refrigerant Line Size¹
Liquid Line Size (“O.D.) 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
Sucon Line Size (“O.D.) 3/4" 3/4" 3/4" 7/8" 1 1/8" 1 1/8" 1 1/8"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
Sucon Valve Size (“O.D.) 3/4" 3/4" 7/8” 7/8" 7/8” 7/8" 7/8"
Valve Connecon Type Sweat Sweat Sweat Sweat Sweat Sweat Sweat
Refrigerant Charge (oz.) 140 150 160 175 180 231 291

Volts/Phase (60 Hz) 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Minimum Circuit Ampacity ² 12.2 14.7 18.0 18.9 22.1 26.2 37
Max. Overcurrent Protecon ³ 20 25 30 30 35 45 60
Min / Max Volts 197/253 197/253 197/253 197/253 197/253 197/253 197/253
Electrical Conduit Size 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4" 1/2" or 3/4"

Equipment Weight 174 180 186 220 226 250 306
Shipping Weight 189 200 206 240 237 270 326
 NO
 
Proper sizing and installaon of equipment is crical to achieving opmal performance. Split system air condioners and heat pumps must
be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your contractor for details or visit www.energystar.gov.
The www.energystar.gov website provides up-to-date system combinaons cered to meet ENERGY STAR requirements. See Page 21 for all ENERGY STAR cered combinaons
as of this documents revision date.
¹ Tested and rated in accordance with AHRI Standard 210/240
² Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.

Always check the S&R plate for electrical data on the unit being installed.
Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.
Installaon of these units requires the specied TXV Kit to be installed on the indoor coil.
THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.