Specifications

4 www.goodmanmfg.com SS-GMBVC
SS-GMBVC www.goodmanmfg.com 5
Airflow Data
           
MBVC1201A*
A Low 420 415 400 400 395 390 390 390 380
B Low 550 545 540 540 535 530 530 525 520
C Low 680 675 670 665 660 655 655 650 640
D Low 810 805 800 800 800 795 790 785 785
A High 615 605 600 600 595 590 590 585 580
B High 805 805 800 800 800 795 790 785 780
C High 1010 1005 1000 1000 995 995 990 985 975
D High 1210 1205 1200 1200 1200 1195 1195 1190 1180
MBVC1601A*
A Low 690 680 670 665 660 655 625 595 575
B Low 850 830 800 795 790 785 775 750 725
C Low 980 970 940 935 930 910 890 865 860
D Low 1110 1085 1070 1055 1045 1025 1000 990 975
A High 1045 1015 1000 990 975 950 935 920 900
B High 1245 1215 1200 1180 1175 1165 1150 1130 1115
C High 1415 1410 1400 1365 1360 1350 1340 1330 1320
D High 1605 1600 1600 1540 1530 1520 1510 1500 1490
MBVC2001A*
A Low 835 815 800 800 795 795 790 775 750
B Low 1075 1070 1070 1065 1050 1045 1045 1040 1035
C Low 1210 1205 1200 1200 1195 1190 1190 1185 1175
D Low 1345 1340 1340 1320 1320 1315 1315 1305 1305
A High 1210 1205 1200 1195 1150 1150 1145 1135 1115
B High 1610 1605 1600 1540 1535 1535 1530 1520 1510
C High 1830 1805 1800 1785 1760 1760 1755 1750 1715
D High 2020 2010 2000 1995 1995 1970 1970 1965 1955

S1 S2 
MBVC1201

MBVC1601

MBVC2001

o o A 600 1000 1200
on o B 800 1200 1600
o on C 1000 1400 1800
on on D 1200 1600 2000

 
S3 S4 Trim Value S5 S6
o o 0 o o A
on o 10% on o B
o on -10% o on C
on on 0 on on D

The chart is for informaon only. For sasfactory operaon, external stac pressure must not exceed value shown on rang plate.
Use the CFM adjustment factors of .98 for horizontal le, .95 for horizontal right & .96 for downow orientaons.