Specifications

4 www.goodmanmfg.com SS-GSZ14
SS-GSZ14 www.goodmanmfg.com 5
Product Specifications (cont.)
GSZ14
0361K*
GSZ14
0371A*
GSZ14
0421K*
GSZ14
0481K*
GSZ14
0491K*
GSZ14
0601K*

Cooling (BTU/h) 36,000 33,000 42,000 48,000 48,000 60,000
Heang (BTU/h)
36,000 34,000 42,000 48,000 48,000 60,000
Decibels 74 73 75 75 76 76

RLA 15.4 14.1 16.7 18.5 19.9 26.4
LRA 83.9 72.2 109.0 124.0 109.0 134.0
Type Scroll Scroll Scroll Scroll Scroll Scroll

Horsepower 1/6 1/4 1/6 1/4 1/6 1/4
FLA 0.95 1.30 1.1 1.30 1.1 1.30

Refrigerant Line Size¹
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ⅞" ⅞" 1⅛" 1⅛" 1⅛" 1⅛"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ¾" ⅞" ⅞" ⅞” ⅞" ⅞"
Standard Line Set Length (max. feet) 80 80 80 80 80 80
Long Line Set Length (max. feet) ²
Equivalent Length 250 250 250 250 250 250
Linear Length 200 200 200 200 200 200
Vercal Length (outdoor below indoor) 80 80 80 80 80 80
Vercal Length (outdoor above indoor) 80 200 80 80 80 80
Valve Connecon Type Sweat Sweat Sweat Sweat Sweat Sweat
Refrigerant Charge 115 175 153 157 192 205

Volts/Phase (60 Hz)
208-230/1 208-230/1 208-230/1 208-230/1 208-230/1 208-230/1
Minimum Circuit Ampacity ³
20.2 18.9 22.0 24.4 26.0 34.3
Max. Overcurrent Protecon ⁴
35 30 35 40 45 60
Min / Max Volts
197 / 253 197/253 197 / 253 197 / 253 197 / 253 197 / 253
Electrical Conduit Size
½" or ¾" 1/2" or 3/4" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"

Equipment Weight (lbs.)
173 220 191 226 273 277
Ship Weight (lbs)
184 240 207 237 288 292

NO NO NO
 
Proper sizing and installaon of equipment is crical to achieving opmal performance. Split system air condioners and heat pumps must
be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your contractor for details or visit www.energystar.gov.
The www.energystar.gov website provides up-to-date system combinaons cered to meet ENERGY STAR requirements. See Page 24 for all ENERGY STAR cered combinaons
as of this document’s revision date.
¹ Tested and rated in accordance with ARI Standard 210/240
² Reference TP-107* for addional applicaon requirements
³ Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.

Always check the S&R plate for electrical data on the unit being installed.
Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.
Installaon of these units requires the specied TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT
THE INDOOR COIL.