Specifications
Table Of Contents
30 www.goodmanmfg.com SS-GSZ14
SS-GSZ14 www.goodmanmfg.com 31
Expanded Heating Data (cont.)
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5
MBh 51.58 48.34 45.15 42.02 40.00 38.54 34.80 31.31 28.47 26.37 24.83 24.00 22.93 20.27 17.60 14.93 12.27
T/R 37.9 35.5 33.2 30.9 29.4 28.3 25.6 23.0 20.9 19.4 18.2 17.6 16.9 14.9 12.9 11.0 9.0
kW 3.41 3.34 3.27 3.21 3.17 3.14 3.08 3.01 2.94 2.88 2.81 2.77 2.74 2.68 2.61 2.54 2.48
Amps 16.5 15.2 14.0 13.0 12.5 12.2 11.4 10.7 10.2 9.6 9.1 8.8 8.6 8.0 7.5 6.8 6.1
COP 4.44 4.24 4.04 3.84 3.70 3.60 3.32 3.05 2.84 2.69 2.59 2.54 2.45 2.22 1.98 1.72 1.45
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5
MBh 56.58 53.20 49.88 46.61 44.50 42.97 39.18 35.56 32.58 30.41 28.84 28.00 26.90 24.15 21.40 18.65 15.90
T/R 33.7 31.7 29.7 27.8 26.5 25.6 23.3 21.2 19.4 18.1 17.2 16.7 16.0 14.4 12.7 11.1 9.5
kW 3.51 3.48 3.44 3.40 3.38 3.36 3.33 3.29 3.25 3.22 3.18 3.16 3.14 3.10 3.07 3.03 2.99
Amps 17.2 15.8 14.6 13.6 13.0 12.6 11.8 11.1 10.5 9.9 9.4 9.0 8.8 8.2 7.6 7.0 6.2
COP 4.72 4.49 4.25 4.02 3.86 3.74 3.45 3.17 2.94 2.77 2.66 2.60 2.51 2.28 2.04 1.80 1.56
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5
MBh 59.32 55.59 51.92 48.32 46.00 44.32 40.01 36.01 32.74 30.32 28.55 27.60 26.37 23.31 20.24 17.17 14.11
T/R 39.2 36.8 34.3 32.0 30.4 29.3 26.5 23.8 21.7 20.1 18.9 18.3 17.4 15.4 13.4 11.4 9.3
kW 3.96 3.87 3.79 3.70 3.64 3.61 3.52 3.43 3.34 3.25 3.16 3.11 3.08 2.99 2.90 2.81 2.72
Amps 19.1 17.5 16.2 15.1 14.5 14.1 13.2 12.4 11.7 11.1 10.5 10.1 9.9 9.3 8.6 7.9 7.1
COP 4.39 4.21 4.02 3.83 3.70 3.60 3.33 3.08 2.87 2.73 2.64 2.60 2.51 2.29 2.05 1.79 1.52
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5
MBh 75.71 71.04 66.44 61.91 59.00 56.89 51.54 46.52 42.41 39.39 37.18 36.00 34.47 30.63 26.80 22.97 19.13
T/R 38.9 36.5 34.2 31.8 30.3 29.3 26.5 23.9 21.8 20.3 19.1 18.5 17.7 15.8 13.8 11.8 9.8
kW 4.91 4.79 4.67 4.55 4.48 4.43 4.31 4.20 4.08 3.96 3.84 3.77 3.72 3.60 3.48 3.36 3.25
Amps 23.4 21.5 19.8 18.4 17.6 17.2 16.1 15.1 14.3 13.5 12.8 12.3 12.0 11.2 10.4 9.5 8.5
COP 4.52 4.35 4.17 3.99 3.86 3.76 3.50 3.25 3.05 2.92 2.84 2.80 2.71 2.49 2.25 2.00 1.73
Calculaons are based on nominal CFM and 70°F indoor dry bulb. Amps = Outdoor unit amps (comp.+fan)
Note: Shaded area is AHRI Rang Condions at 47°F outdoor ambient temperature. kW = Total system power