Specifications
Table Of Contents
2 www.goodmanmfg.com SS-GSZ14
SS-GSZ14 www.goodmanmfg.com 3
Product Specifications
GSZ14
0181K*
GSZ14
0191A*
GSZ14
0241K*
GSZ14
0251A*
GSZ14
0301K*
GSZ14
0311A*
Cooling (BTU/h) 18,000 17,400 24,000 23,200 30,000 28,000
Heang (BTU/h)
18,000 18,000 24,000 23,200 30,000 31,000
Decibels 72 72 72 72 74 75
RLA 9.0 9.0 10.9 10.9 13.5 13.5
LRA 47.5 47.5 62.9 62.9 72.5 72.5
Type Scroll Scroll Scroll Scroll Scroll Scroll
Horsepower 1/6 1/6 1/6 1/6 1/6 1/6
FLA 0.95 1.1 0.95 1.1 0.95 1.10
Refrigerant Line Size¹
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ¾" ¾" ¾" ¾" ¾" ¾"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ¾" ¾" ¾" ¾" ¾" ¾”
Standard Line Set Length (max. feet) 80 80 80 80 80 80
Long Line Set Length (max. feet) ²
Equivalent Length 250 250 250 250 250 250
Linear Length 200 200 200 200 200 200
Vercal Length (outdoor below indoor) 80 80 80 80 80 80
Vercal Length (outdoor above indoor) 80 200 80 200 80 200
Valve Connecon Type Sweat Sweat Sweat Sweat Sweat Sweat
Refrigerant Charge (oz.) 108 108 108 108 108 160
Volts/Phase (60 Hz)
208-230/1 208-230/1 208-230/1 208-230/1 208-230/1 208-230/1
Minimum Circuit Ampacity ³
12.2 12.4 14.6 14.7 17.8 17.9
Max. Overcurrent Protecon ⁴
20 20 25 25 30 30
Min / Max Volts
197 / 253 197 / 253 197 / 253 197 / 253 197 / 253 197/253
Electrical Conduit Size
½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾" 1/2" or 3/4"
Equipment Weight (lbs.)
143 143 143 143 171 186
Ship Weight (lbs)
154 154 154 154 182 206
NO NO NO
Proper sizing and installaon of equipment is crical to achieving opmal performance. Split system air condioners and heat pumps must
be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your contractor for details or visit www.energystar.gov.
The www.energystar.gov website provides up-to-date system combinaons cered to meet ENERGY STAR requirements. See Page 24 for all ENERGY STAR cered combinaons
as of this document’s revision date.
¹ Tested and rated in accordance with ARI Standard 210/240
² Reference TP-107* for addional applicaon requirements
³ Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
⁴ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
• Always check the S&R plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installaon Instrucons Final Charge Procedure.
• Installaon of these units may require the specied TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT
NOT THE INDOOR COIL.