Service Manual
INSTALLATION CONSIDERATIONS
27
and outside of the wall. The wall penetration should be sealed
with silicone caulking material.
12345678
2 120 115 110 105 100 95 90 85
3 134 127 120 113 106 99 92 85
2 100 95 90 85 80 75 70 65
3 151 144 137 130 123 116 109 102
2 4540353025201510
3 113 106 99 92 85 78 71 64
2 706560555045N/AN/A
3 8982756861544740
2 N/A N/A N/A N/A N/A N/A N/A N/A
31201131069992857871
2 N/A N/A N/A N/A N/A N/A N/A N/A
3 151 144 137 130 123 116 109 102
2 N/A N/A N/A N/A N/A N/A N/A N/A
3 151 144 137 130 123 116 109 102
2 120 115 110 105 100 95 N/A N/A
3 185 178 171 164 157 150 143 136
2 8580757065605550
3 168 161 154 147 140 133 126 119
2 40353025201510 5
31201131069992857871
2 N/A N/A N/A N/A N/A N/A N/A N/A
3 113 106 99 92 85 78 71 64
2 N/A N/A N/A N/A N/A N/A N/A N/A
3 151 144 137 130 123 116 109 102
*MV96C0403BN
*MVC96/*CVC96 Direct Vent (2 - Pipe) and Non-Direct Vent (1- Pipe)
(6)
Maximum Allowable Length of Vent/Flue Pipe
MODEL
Pipe Size
(4)
(in.)
Number of Elbows
(3) (5)
*CVC960603BN
*CVC960804CN
*CVC961005CN
*CVC961205DN
*MVC960603BN
*MVC960803BN
*MVC960804CN
*MVC961005CN
*MVC961205DN
*CVC960403BN
*MVC961005DN
1) Maximum allowable limits listed on individual lengths for inlet and flue
and NOT a combination.
2) Minimum requirement for each vent pipe is five (5) feet in length and
one elbow/tee.
3) Tee used in the vent/flue termination must be included when deter-
mining the number of elbows in the piping system.
4) 2 1/2” or 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg.
Long Sweep
elbows should be considered equivalent to one 90 deg. elbow.
6) One 90° elbow should be secured to the combustion air intake con-
nection.
AIR
INTAKE
90°
ELBOWS
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
3” - 24”
90% Alternate Horizontal Vent Termination (Dual Pipe)
90º OR 45°
ELBOW
12" MIN. TO GRADE OR
HIGHEST ANTICIPATED
SNOW LEVEL
6” MAX
10”- 24”
4” MIN
Standard Horizontal Terminiations (Dual Pipe)
Vent & Combustion Air Intake Measurements for Stan-
dard Horizontal Terminations (Dual Pipe)
Center to center = 10” min / 24” max.
Vertical separation: 0” - 24”
Vent termination from wall = 8” min / 12” max.
Combustion air intake from wall = 6” max.
Vent and intake clearance to ground
or anticipated snow level = 12” min.