Airflow Data
GCVC960403BNA
Cooling Speeds
( @ .1" - .8" w.c. ESP)
GCVC960403BNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 20 - 50°F)
Tap Adjust
High-Stage
CFM
Low-Stage
CFM
Tap Adjust
High-Stage
CFM
Low-Stage
CFM
Rise
(°F)
A
Minus 10% 590 404
A
Minus 10% 861 614 41
Minus 5% 622 427 Minus 5% 909 648 39
Normal 655 449 Normal 957 682 37
Plus 5% 688 471 Plus 5% 1,005 716 35
Plus 10% 721 494 Plus 10% 1,053 750 34
B
Minus 10% 726 512
B
Minus 10% 953 675 37
Minus 5% 767 541 Minus 5% 1,006 713 35
Normal 807 569 Normal 1,059 750 34
Plus 5% 847 597 Plus 5% 1,112 788 32
Plus 10% 888 626 Plus 10% 1,165 825 31
C
Minus 10% 898 644
C
Minus 10% 1,040 738 34
Minus 5% 948 680 Minus 5% 1,097 779 32
Normal 998 716 Normal 1,155 820 31
Plus 5% 1,048 752 Plus 5% 1,213 861 29
Plus 10% 1,098 788 Plus 10% 1,271 902 28
D
Minus 10% 1,086 769
D
Minus 10% 1,126 799 32
Minus 5% 1,147 811 Minus 5% 1,188 844 30
Normal 1,207 854 Normal 1,251 888 28
Plus 5% 1,267 897 Plus 5% 1,314 932 27
Plus 10% 1,328 939 Plus 10% 1,376 977 26
GCVC960603BNA
Cooling Speeds
( @ .1" - .8" w.c. ESP)
GCVC960603BNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 35 - 65°F)
Tap Adjust
High-Stage
CFM
Low-Stage
CFM
Tap Adjust
High-Stage
CFM
Low-Stage
CFM
Rise
(°F)
A
Minus 10% 590 390
A
Minus 10% 844 618 63
Minus 5% 623 411 Minus 5% 891 653 60
Normal 656 433 Normal 938 687 57
Plus 5% 689 455 Plus 5% 985 721 54
Plus 10% 722 476 Plus 10% 1,032 756 52
B
Minus 10% 711 487
B
Minus 10% 855 676 62
Minus 5% 751 514 Minus 5% 903 713 59
Normal 790 541 Normal 950 751 56
Plus 5% 830 568 Plus 5% 998 789 53
Plus 10% 869 595 Plus 10% 1,045 826 51
C
Minus 10% 875 617
C
Minus 10% 887 733 60
Minus 5% 923 652 Minus 5% 937 773 57
Normal 972 686 Normal 986 814 54
Plus 5% 1,021 720 Plus 5% 1,035 855 52
Plus 10% 1,069 755 Plus 10% 1,085 895 49
D
Minus 10% 1,076 725
D
Minus 10% 893 787 60
Minus 5% 1,135 766 Minus 5% 942 830 57
Normal 1,195 806 Normal 992 874 54
Plus 5% 1,255 846 Plus 5% 1,042 918 51
Plus 10% 1,315 887 Plus 10% 1,091 961 49
Notes
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.