Installation Manual
10
• Profile D ramps up to 50% of the demand for 1/2 minute, then
ramps to 82% of the full cooling demand airflow and operates
there for approximately 7 1/2 minutes. The motor then steps
up to the full demand airflow. Profile D has a 1/2 minute at 50%
airflow OFF delay.
OFF
OFF
Airflow Tables
STATUS
The current system operational mode and requested indoor CFM
is reported in this menu. This information can be used for trouble-
shooting purposes.
• Red communications LED - Indicates the status of the
network. The table below indicates the LED status and
the corresponding potential problem.
• Green receive LED - Indicates network traffic. The table
below indicates the LED status and the corresponding
potential problem.
• LEARN button - Used to reset the network. Depress the
button for approximately 2 seconds to reset the network.
SYSTEM T ROUBLESHOOTING
NOTE: Refer to the instructions accompanying the CT compatible
indoor air handler/furnace/modular blower unit for
troubleshooting information.
Refer to the Troubleshooting Chart at the end of this manual for a
listing of possible air conditioner and heat pump error codes,
possible causes and corrective actions.