Specifications


2 www.goodmanmfg.com SS-GSXC16
SS-GSXC16 www.goodmanmfg.com 3
GSXC16
0241C*
GSXC16
0361C*
GSXC16
0481C*
GSXC16
0601C*

Nominal Cooling (BTU/h) 24,000 36,000 48,000 60,000
Decibels (High/Low)
4
71/70 71/70 72/71 74/70

RLA 10.0 14.8 20.4 22.9
LRA 62.9 84.2 122.1 147.2

Horsepower (RPM) 1/6 1/6 1/6 1/3
FLA 1.1 1.2 1.2 2.8

Refrigerant Line Size¹
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ¾" ⅞" 1⅛" 1⅛"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ¾" ¾" ⅞" ⅞"
Valve Connecon Type Sweat Sweat Sweat Sweat
Refrigerant Charge 92 114 177 191

Voltage-Hz 208/230-1 208/230-1 208/230-1 208/230-1
Minimum Circuit Ampacity ² 13.6 19.7 26.7 31.4
Max. Overcurrent Protecon ³ 20 30 45 50
Min / Max Volts 197/253 197/253 197/253 197/253
Power Supply ½" or ¾" ½" or ¾" ½" or ¾" ½" or ¾"
 180 201 263 304
 197 223 285 326
ENERGY STAR®

Proper sizing and installaon of equipment is crical to achieving opmal performance. Split system air
condioners and heat pumps must
be matched with appropriate coil components to meet ENERGY STAR crite-
ria. Ask your contractor for details or visit www.energystar.gov.
The www.energystar.gov website provides up-to-date system combinaons cered to meet ENERGY
STAR requirements.
See Pages 20-21 for all ENERGY STAR cered combinaons as of this document’s revision date.
¹ Tested and rated in accordance with AHRI Standard 210/240
² Wire size should be determined in accordance with Naonal
Electrical Codes; extensive wire runs will require larger wire sizes
³ Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
4
Sound dBa rangs are based upon ANSI/AHRI Standard 220.
Accordingly, all sound power levels are A-weighted.

Always check the S&R plate for electrical data on the unit being installed.
Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must
be adjusted per Installaon Instrucons Final Charge Procedure.
Installaon of these units requires the specied TXV Kit to be installed on the indoor coil.
THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT, NOT THE INDOOR COIL.