Service Manual
74
SERVICING
Checking ECM Motors
ECM motors connect directly to the AC Line Voltage. DO
NOT insert contactors in series with the ECM Motor AC
Line. The control is powered continuously to insure reliable
start-up. The connector plug is polarized, verify and reverify
correct connector orientation before applying power. DO
NOT force plug into motor and make sure power is off be-
fore inserting power connector. DO NOT apply voltage to
terminals 1 or 2.
General Checks/Considerations
1. Check power supply to the furnace. Ensure power sup-
ply is within the range specified on rating plate. See
section S-1.
2. Check motor power harness. Ensure wires are continu-
ous and make good contact when seated in the connec-
tors. Repair or replace as needed.
3. Check motor control harness. Ensure wires are con-
tinuous and make good contact when seated in the con-
nectors. Repair or replace as needed.
4. Check thermostat and thermostat wiring. Ensure ther-
mostat is providing proper cooling/heating/continuous fan
demands. Repair or replace as needed.
5. Check blower wheel. Confirm wheel is properly seated
on motor shaft. Set screw must be on shaft flat and
torqued to 165 in-lbs minimum. Confirm wheel has no
broken or loose blades. Repair or replace as needed.
6. Ensure motor and wheel turn freely. Check for interfer-
ence between wheel and housing or wheel and motor.
Repair or replace as needed.
7. Check housing for cracks and/or corrosion. Repair or
replace as needed.
8. Check motor mounting bracket. Ensure mounting bracket
is tightly secured to the housing. Ensure bracket is not
cracked or broken.
Emerson UltraCheck-EZ
TM
Diagnostic Tool
The Emerson UltraCheck-EZ
TM
diagnostic tool may be used
to diagnose the ECM motor.
HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.
To use the diagnostic tool, perform the following steps:
1. Disconnect power to the furnace.
2. Disconnect the 4-circuit control harness from the motor.
3. Plug the 4-circuit connector from the diagnostic tool into
the motor control connector.
4. Connect one alligator clip from the diagnostic tool to a
ground source.
5. Connect the other alligator clip to a 24VAC source.
NOTE: The alligator clips are NOT polarized.
NOTE: The UltraCheck-EZ
TM
diagnostic tool is equipped with
a nonreplaceable fuse. Connecting the tool to a source
other than 24VAC could damage the tool and cause the
fuse to open. Doing so will render the diagnostic tool
inoperable.
6. Turn on power to the furnace.
WARNING
Line Voltage now present.
7. Depress the orange power button on the diagnostic tool
to send a run signal to the motor. Allow up to 5 seconds
for the motor to start.
NOTE: If the orange power button does not illuminate when
depressed, the tool either has an open fuse or is not prop-
erly connected to a 24VAC source.
8. The green LED on the diagnostic tool will blink indicating
communications between the tool and motor. See table
below for indications of tool indicators and motor actions.
Replace or repair as needed.
Power
Button
Green
LED
Motor
Action
Indication(s)
OFF OFF
Not
Rotating
Confirm 24VAC to
UltraCheck-EZ
TM
tool.
If 24VAC is confirmed,
diagnostic tool is
inoperable.
ON Blinking Rotating
Motor and control/end
bell are functioning
properly.
ON OFF Rotating
Replace motor
control/end bell.
ON Blinking
Not
Rotating
Check motor (see
Motor Check s below).
ON OFF
Not
Rotating
Replace motor
control/end bell; verify
motor (see Motor
Checks below).
9. Depress the orange power button to turn off motor.
10. Disconnect power. Disconnect diagnostic tool.
11. Reconnect the 4-wire harness from control board to
motor.