Service Manual

SYSTEM OPERATION
59
Venting
The venting system should be planned and installed with
the following in mind;
Should not be longer than necessary
Use 45°elbows rather than 90° elbows when possible
Must not sag or otherwise trap condensate
Use longest radius fittings possible
If using 3" venting, make the transition from 2" to 3"
as close as practically possible
Make sure there is no flue gas recirculation into the
combustion air pipe
Condensate Drainage
Furnace combustion can be affected if a furnace is holding
condensate. Check for proper connections of drain hoses,
make sure furnace condensate trap is clean. Make sure
furnace is not improperly sloped. Make sure air condition-
ing coil drain is not interfering with furnace drain.
Other Causes
1. Manifold Gas Pressure must be set for the gas being
used, Natural or L.P., high and low firing rates. If con-
verted to L.P. gas, check size of all orifices
2. Remove Draft Inducer, Check the integrity of the gasket
between the inducer and the collector box cover, any air
leak here will have a negative effect on combustion.
Check the orifice hole in the collector box, it must be
free of burrs on both sides
3. Make sure burners are clean, not out of position and line
up correctly with exchanger tubes, including the heat
exchanger orifice plate between the burners and the heat
exchanger tubes, make sure it is not loose, missing a
screw or hanging down between the burners and heat
exchangers causing flame impingement.
4. Make sure the field installed gas line is not binding and
causing distortion of burner assembly
5. If the furnace is installed as a one pipe system; make
sure the surrounding area and structure are adequate
to provide combustion air
6. Make sure there are no cabinet air leaks allowing sup-
ply air to affect combustion
7. If heat exchanger integrity is uncertain, follow proce-
dures in Service Bulletin SF-041
ComfortNet™ System