Technical Information
FURNACE SPECIFICATIONS
19
1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation.
2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level. The furnace must not be derated, orifice
changes should only be made if necessary for altitude.
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufactures method in accordance with the
"A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total
heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times
output.
4. Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps.
ADVC8***A*
MODEL
ADVC80603B*A* ADVC80805C*A* ADVC81005C*A*
Btuh Input (US) High Fire 70,000 90,000
115,000
Output (US) High Fire 56,000 72,000
92,000
Btuh Input (US) Low Fire 51,000 63,000
80,500
Output (US) Low Fire 40,800 50,400
64,400
A.F.U.E. 80% 80%
80%
Rated External Static (" w.c.) .10 - .50 .10 - .50
.10 - .50
Temperature Rise (°F) 30 - 60 35 - 65 35 - 65
High Stage Pressure Switch Trip Point (" w.c.) -0.55 -0.55
-0.55
Low Stage Pressure Switch Trip Point (" w.c.) -0.30 -0.30
-0.30
Blower Wheel (D" x W") 10 x 8 10 x 10 10 x 10
Blower Horsepower 3/4 3/4 3/4
Blower Speeds
Max CFM @ 0.5 E.S.P.
Power Supply 115-60-1 115-60-1
115-60-1
Minimum Circuit Ampacity (MCA) 12.1 12.1
12.1
Maximum Overcurrent Device 15 15
15
Transformer (VA) 40 40
40
Heat Anticipator (Amps) 0.7 0.7
0.7
Primary Limit Setting (°F) 190 190
200
Auxiliary Limit Setting (°F) 120 120 120
Rollout Limit Setting (°F) 300 300
300
Fan Delay On Heating 30 secs. 30 secs.
30 secs.
Off Heating * 150 secs. 150 secs.
150 secs.
Fan Delay On Cooling 5 secs. 5 secs. 5 secs.
Off Cooling 45 secs. 45 secs.
45 secs.
Fan Delay On - Fan Only 5 secs. 5 secs.
5 secs.
Gas Supply Pressure (Natural/Propane) (" w.c.) 7 / 11 7 / 11
7 / 11
Manifold Pressure (Natural/Propane) High Stage (" w.c.) 3.5 / 10 3.5 /10
3.5 /10
Manifold Pressure (Natural/Propane) Low Stage ("w.c.) 1.9 / 6.0 1.9 / 6.0
1.9 / 6.0
Orifice Size (Natural/Propane) #43 / #55 #43 / #55
#43 / #55
Number of Burners 3 4
5
Vent Connector Diameter (inches) 4 4
4
Shipping Weight (lbs.) 112 124
130
Refer to airflow charts in this manual.
* Off Heating - This fan delay timing is adjustable (90, 120, 150 or 180 seconds), 150 seconds as shipped.