Condensing Unit & Heat Pump R410A Service Manual

84
Complaint
System
Operating
Pressures
POSSIBLE CAUSE
DOTS IN ANALYSIS
GUIDE INDICATE
"POSSIBLE CAUSE"
SYMPTOM
System will not start
Compressor will not start - fan runs
Comp. and Cond. Fan will not start
Evaporator fan will not start
Condenser fan will not start
Compressor runs - goes off on overload
Compressor cycles on overload
System runs continuously - little cooling/htg
Too cool and then too warm
Not cool enough on warm days
Certain areas too cool, others too warm
Compressor is noisy
System runs - blows cold air in heating
Unit will not terminate defrost
Unit will not defrost
Low suction pressure
Low head pressure
High suction pressure
High head pressure
Test Method
Remedy
See Service Procedure Ref.
Pow er Failure
Test Voltage S-1
Blow n Fuse
Inspect Fuse Size & Type S-1
Unbalanced Pow er, 3PH
Test Voltage S-1
Loose Connection
Inspect Connection - Tighten S-2, S-3
Shorted or Broken Wires
Test Circuits With Ohmmeter S-2, S-3
Open Fan Overload
Test Continuity of Overload S-17A
Faulty Thermostat
Test Continuity of Thermostat & Wiring S-3
Faulty Transf ormer
Check Control Circuit w ith Voltmeter S-4
Shorted or Open Capacitor
Test Capacitor S-15
Internal Compressor Overload Open
Test Continuity of Overload S-17A
Shorted or Grounded Compressor
Test Motor Windings S-17B
Compressor Stuck
Use Test Cord S-17D
Faulty Compressor Contactor
Test Continuity of Coil & Contacts S-7, S-8
Faulty Fan Relay
Test Continuity of Coil And Contacts S-7
Open Control Circuit
Test Control Circuit w ith Voltmeter S-4
Low Voltage
Test Voltage S-1
Faulty Evap. Fan Motor
Repair or Replace S-16
Shorted or Grounded Fan Motor
Test Motor Windings S-16
Improper Cooling Anticipator
Check Resistance of Anticipator S-3B
Shortage of Refrigerant
Test For Leaks, Add Ref rigerant S-101,103
Restricted Liquid Line
Remove Restriction, Replace Restricted Part S-112
Open Element or Limit on Elec. Heater
Test Heater Element and Controls S-26,S-27
Dirty Air Filter
Inspect Filter-Clean or Replace
Dirty Indoor Coil
Inspect Coil - Clean
Not enough air across Indoor Coil
Check Blow er Speed, Duct Static Press, Filter S-200
Too much air across Indoor Coil
Reduce Blow er Speed S-200
Overcharge of Refrigerant
Recover Part of Charge S-113
Dirty Outdoor Coil
Inspect Coil - Clean
Noncondensibles
Recover Charge, Evacuate, Recharge S-114
Recirculation of Condensing Air
Remove Obstruction to Air Flow
Infiltration of Outdoor Air
Check Window s, Doors, Vent Fans, Etc.
Improperly Located Thermostat
Relocate Thermostat
Air Flow Unbalanced
Readjust Air Volume Dampers
System Undersized
Refigure Cooling Load
Broken Internal Parts
Replace Compressor S-115
Broken Valves
Test Compressor Eff iciency S-104
Inefficient Compressor
Test Compressor Eff iciency S-104
Wrong Type Expansion Valve
Replace Valve S-110
Expansion Device Restricted
Remove Restriction or Replace Expansion Device S-110
Oversized Expansion Valve
Replace Valve
Undersized Expansion Valve
Replace Valve
Expansion Valve Bulb Loose
Tighten Bulb Bracket S-105
Inoperative Expansion Valve
Check Valve Operation S-110
Loose Hold-dow n Bolts
Tighten Bolts
Faulty Reversing Valve
Replace Valve or Solenoid S-21, 122
Faulty Defrost Control
Test Control S-24
Faulty Defrost Thermostat
Test Def rost Thermostat S-25
Flow rator Not Seating Properly
Check Flow rator & Seat or Replace Flow rator S-111
Cooling or Heating Cycle (Heat Pump)
COOLING/HP ANALYSIS CHART
No Cooling
Unsatisfactory
Cooling/Heating
Heating Cycle Only (Heat Pum p)
TROUBLESHOOTING CHART
TROUBLESHOOTING CHART