59
AIRFLOW DATA
X = Outside of Temperature Rise Range - Not Recommended.
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,
external static pressure should not exceed 0.8" w.c.
GPG16
CFM WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
0.1
625 53 54 855 107 53 625 51 850 104 1,090 197
0.2
585 61 58 815 114 55 590 60 810 116 1,055 201
0.3
550 70 61 785 125 57 555 68 775 122 1,020 207
0.4
495 78 X 750 135
60
505 79 735 129 995 212
0.5
445 85 X 705 141
64
450 86 705 136 955 230
0.6
400 93 X 660 149
X
410 93 655 147 915 240
0.7
345 99 X 615 157
X
330 101 600 154 880 255
0.8 ---- ---- ---- 570 166 X ---- ---- 565 160 835 246
CFM WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
0.1
1,035 156 43 1,300 287 46 945 130 1,095 185 1,295 289
0.2
990 165 45 1,265 293 47 905 136 1,055 195 1,260 294
0.3
950 173 47 1,220 310 49 865 143 1,020 202 1,220 304
0.4
910 184 49 1,190 306
50
815 152 970 210 1,180 313
0.5
865 190 52 1,145 319
52
770 160 930 215 1,140 319
0.6
820 200 55 1,105 320
54
715 173 885 222 1,105 326
0.7
765 204 59 1,070 330
56
660 173 840 233 1,055 334
0.8 725 211 62 1,015 338 59 610 183 785 234 1,015 337
CFM WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
0.1
950 115 47 1,245 230 48 1,045 149 1,280 258 1,440 354
0.2
895 124 50 1,195 238 50 990 160 1,225 259 1,390 365
0.3
840 134 54 1,150 247 52 935 167 1,180 274 1,355 369
0.4
775 146 58 1,095 256
55
875 179 1,130 280 1,300 383
0.5
710 152 63 1,045 263
57
820 186 1,085 293 1,260 396
0.6
650 160 X 990 277
61
755 194 1,030 295 1,210 402
0.7
590 163 X 935 285
64
700 197 975 304 1,160 397
0.8 540 171 X 870 288 X 650 214 920 315 1,110 415
GPG1624060M41** - Rise Range: 35° - 65°
E.S.P.
T1 LOW STAGE HEATING
SPEED
T2 HIGH STAGE HEATING
SPEED
T3 LOW STAGE
COOLING SPEED
T4 HIGH STAGE
COOLING SPEED
T5 COOLING SPEED
GPG1630080M41** - Rise Range: 35° - 65°
E.S.P.
T1 LOW STAGE HEATING
SPEED
T2 HIGH STAGE HEATING
SPEED
T3 LOW STAGE
COOLING SPEED
T4 HIGH STAGE
COOLING SPEED
T5 COOLING SPEED
GPG1636080M41** - Rise Range: 35° - 65°
E.S.P.
T1 LOW STAGE HEATING
SPEED
T2 HIGH STAGE HEATING
SPEED
T3 LOW STAGE
COOLING SPEED
T4 HIGH STAGE
COOLING SPEED
T5 COOLING SPEED