GPG16M Service Manual

SERVICING
57
Flame
Sensor
Flame Sensor
2. Connect a microamp meter in series with this wire and
terminal FS.
3. Be sure the negative side of the meter is to the wire and
the positive of the meter is to terminal FS.
4. Turn on Power.
WARNING
Line Voltage now present.
5. With Power ON, Place the unit into a heating cycle.
6. As soon as flame is established a microamp reading
should be evident once proof of flame (microamp reading)
is established, the hot surface ignitor will be de-ener-
gized.
7. The nominal microamp reading is 4 microamps.
8. If the microamp current is less than 0.5 microamp the
control will lockout and flash a code of 1 flash after
attempting to reestablish flame sense.
9. If the microamp reading is less than the minimum speci-
fied, check for high resistance wiring connections, the
distance (3/16") between the sensor and burner, flame
sensor connections, dirty flame sensor or poor ground-
ing.
10. If no reading, check for continuity on all components and
if good - replace ignition control module.
NOTE: Contaminated fuel or combustion air can create a
nearly invisible coating on the flame sensor. This coating
works as an insulator causing a loss in the flame sense
signal. If this situation occurs the flame sensor must be
cleaned with steel wool. Do not use sand paper, the silicone
in sand paper will further contaminate the sensor.