Installation Guide
9
NOTES:
• For servicing or cleaning, a 24” front clearance is required.
• Unit connections (electrical, flue and drain) may necessitate
greater clearances than the minimum clearances listed above.
• In all cases, accessibility clearance must take precedence over
clearances from the enclosure where accessibility clearances are
greater.
Installations must adhere to the clearances to combustible materi-
als to which this furnace has been design certified. The minimum
clearance information for this furnace is provided on the unit’s
clearance label. These clearances must be permanently maintained.
Clearances must also accommodate an installation’s gas, electri-
cal, and drain trap and drain line connections.
NOTE: In addition to the required clearances to combustible mate-
rials, a minimum of 24 inches service clearance must be available
in front of the unit.
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting system serving other appliances, the venting system may be too large to
properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the American National Standard/National Standard of Canada for
Gas-Fired Central Furnaces ANSI Z21.4, CSA-2.3 latest edition Section 1.23.1.
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any
other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system;
2. Inspect the venting system for proper size and horizontal pitch, as required by the National Fuel Gas Code, ANSI Z223.1
or the Natural Gas and Propane Installation Code, CSA B149.1-05 and these instructions. Determine that there is no
blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s)
connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so appliance shall
operate continuously.
7. Test for spillage from draft hood appliances at the draft hood relief opening after 5 minutes of main burner operation.
Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with
the National Fuel Gas Code ANSI Z223.1/NFPA 54 and/or National Gas and Propane Installation Code CSA B149.1-05.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous
conditions of use.
If resizing is required on any portion of the venting system, use the appropriate table in Appendix G in the latest edition of the
National Fuel Gas Code ANSI Z223.1 and/or CSA B149.1-05 Installation Codes.
POSITION* SIDES REAR FRONT BOTTOM FLUE TOP
Counterflow0"0"3"NC0"1"
Horizontal 6" 0" 3" C 0" 6"
C = If placed on combustible floor, floor MUST be wood only.
NC = For installation on non-combustible floors only. A combustible subbase
must
b
e use
d
f
or
i
nsta
ll
at
i
ons on com
b
ust
ibl
e
fl
oor
i
ng.
*CVM97* MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
(INCHES)
TOP
BOTTOM
SIDE SIDE SIDE
TOP
BOTTOM
Upflow Counterflow Horizontal
Figure 3










