Installation Guide

59
TROUBLESHOOTING CODES
Message Code
Furnace fails to operate.
Integrated control module LED
display provides
b5
error code.
ComfortNet thermostatCall for
Service icon illuminated.
ComfortNet thermostat scrolls
Check Furnace” message.
b5
Circulator blower
motor fails to
start 10
consecutive
times.
MTR LCKD
ROTOR
b5
Obstruction in circulator blower
housing.
Seized circulator blower motor
bearings.
Failed circulator blower motor.
Check circulator blower for
obstructions. Remove and
repair/replace wheel/motor if necessary.
Check circulator blower motor shaft
rotation and motor. Replace motor if
necessary.
Turn power OFF prior to repair
Replace motor with correct
replacement part.
Replace wheel with correct
replacement part.
Furnace fails to operate.
Integrated control module LED
display provides
b6
error code.
ComfortNet thermostatCall for
Service icon illuminated.
ComfortNet thermostat scrolls
Check Furnace” message.
b6
Circulator blower
motor shuts
down for over or
under voltage
condition.
Circulator blower
motor shuts
down due to
over temperature
condition on
power module.
MOTOR
VOLTS
b6
High AC line voltage to furnace.
Low AC line voltage to furnace.
High ambient temperatures.
Check power to furnace. Verify line
voltage to furnace is within the range
specified on the furnace rating plate.
See "Product Description" and
"Location Requirements &
Considerations" for furnace
installation requirements.
Turn power OFF prior to repair.
Furnace fails to operate.
Integrated control module LED
display provides
b7
error code.
ComfortNet thermostatCall for
Service icon illuminated.
ComfortNet thermostat scrolls
Check Furnace” message.
b7
Circulator blower
motor does not
have enough
information to
operate properly.
Motor fails to
start 40
consecutive
times.
MOTOR
PARAMS
b7
Error with integrated control
module.
Motor has a locked rotor condition.
Check integrated control module.
Verify control is populated with
correct shared data set. See data
errors above for details.
Check for locked rotor condition
(see error code above for details).
Turn power OFF prior to repair.
Replace with correct replacement
part(s).
Use memory card for the specific
model.
Furnace operates at reduced
performance.
Integrated control module LED
display provides
b9
error code.
b9
Airflow is lower
than demanded.
LOW ID
AIRFLOW
b9
Blocked filters.
Restrictive ductwork.
Undersized ductwork.
Check filters for blockage. Clean filters
or remove obstruction.
Check ductwork for blockage. Remove
obstruction. Verify all registers are fully
open.
Verify ductwork is appropriately sized
for system. Resize/replace ductwork if
necessary.
Turn power OFF prior to repair.
Diagnostic
& Status
LED Codes
Fault
Description
Symptoms of Abnormal Operation
(Non-communicating
& ComfortNet Thermostat)
ComfortNet
Thermostat Only
Possible Causes Corrective Actions Notes & Cautions