Installation Guide
56
TROUBLESHOOTING CODES
Message Code
•
•
•
•
•
Induced draft blower and circulator
blower runs continuously. No
furnace operation.
Integrated control module LED
display provides
E4
error code.
ComfortNet thermostat “ Call for
Service” icon illuminated.
ComfortNet thermostat scrolls
“Check Furnace” message.
E4
•Flame sensed
when it should
not be present.
IMPROPER
FLAME
E4 •
•
•
Short to ground in flame sense
circuit.
Lingering burner flame.
Slow closing gas valve.
•
•
•
Correct short at flame sensor or
in flame sensor wiring.
Check for lingering flame.
Verify proper operation of gas
valve. Replace if necessary.
• Turn power OFF prior to repair.
•
•
•
•
Furnace fails to operate
Integrated control module LED
display provides EC error code.
ComfortNet thermostat “ Call for
Service” icon illuminated.
ComfortNet thermostat scrolls
“Check Furnace” message.
EC
• Inducer motor
overcurrent
fault.
INDUCER
FAULT OR
INDUCER
LOCKOUT
EC • Lingering Inducer motor
overcurrent detected.
•
•
Reset system power and verify
inducer is running properly.
Replace inducer or integrated
control module, if necessary.
•
•
No furnace operation.
Integrated control module LED
display provides
Ed
error code.
Ed
•Manual reset
rollout switch is
open.
ROLLOUT
OPEN
Ed •
•
•
•
Orifice plate out of position.
Blocked heat exchanger.
Burners out of alignment.
Defective heat exchanger.
•
•
•
•
Line up orifice plate.
Remove Blockage from heat
exchanger.
Line up burners.
Check for flame disturbance on
roll out when blower comes on.
• Turn power OFF prior to repair.
•
•
No furnace operation.
Integrated control module LED
display provides Ef error code.
EF
• Open auxiliary
input.
AUXILIARY
OPEN
EF •
•
•
Open circuit between aux in or aux
out.
Missing jumper.
Open float switch.
•
•
Install jumper.
Inspect float switch.
• Turn power OFF prior to repair.
•
•
•
No furnace operation.
Integrated control module LED
display provides
E5
error code.
ComfortNet thermostat displays
“Battery Power”.
E5
• Open Fuse. Not Displayed Not
Displayed
• Short in low voltage wiring • Locate and correct short in
low voltage wiring.
•
•
Turn power OFF prior to repair.
Replace fuse with 3- amp automotive
type
•
•
Normal furnace operation.
Integrated control module LED
display provides
E6
error code.
E6
•Flame sense
micro amp
signal is low.
WEAK
FLAME
E6 •
•
•
Flame sensor is coated/oxidized.
Flame sensor incorrectly
positioned in burner flame.
Lazy burner flame due to improper
gas pressure or combustion air.
•
•
•
Clean flame sensor if coated/oxidized.
Inspect for proper sensor alignment.
Check inlet air piping for blockage,
proper length, elbows, and termination.
Compare current gas pressure to rating
plate. Adjust as needed.
•
•
•
•
Turn power OFF prior to repair.
Clean flame sensor with steel wool.
See "Vent/Flue Pipe" section for
piping details.
See rating plate for proper gas
pressure.
•
•
Furnace fails to operate on high
stage; furnace operates normally
on low stage.
Integrated control module LED
display provides
E8
error code.
E8
•
•
•
High stage
pressure switch
circuit is closed
at start of
heating cycle.
Induced draft
blower is
operating.
Furnace is
operating on
low stage only
PS2
CLOSED
E8 •
•
High stage pressure switch
contacts sticking.
Shorts in pressure switch circuit
wiring.
•
•
Replace high stage pressure switch.
Repair short in wiring
•
•
Turn power OFF prior to repair.
Replace pressure switch with correct
replacement part.
Diagnostic
& Status
LED Codes
Fault
Description
Symptoms of Abnormal Operation
(Non-communicating
& ComfortNet™ Thermostat)
ComfortNet
Thermostat Only
Possible Causes Corrective Actions Notes & Cautions