TROUBLESHOOTING CODES
Message Code
Induced draft blower and circulator
blower runs continuously. No
furnace operation.
Integrated control module LED
display provides
E4
error code.
ComfortNet thermostat Call for
Service icon illuminated.
ComfortNet thermostat scrolls
Check Furnace” message.
E4
•Flame sensed
when it should
not be present.
IMPROPER
FLAME
E4
Short to ground in flame sense
circuit.
Lingering burner flame.
Slow closing gas valve.
Correct short at flame sensor or
in flame sensor wiring.
Check for lingering flame.
Verify proper operation of gas
valve. Replace if necessary.
Turn power OFF prior to repair.
Furnace fails to operate
Integrated control module LED
display provides EC error code.
ComfortNet thermostat Call for
Service icon illuminated.
ComfortNet thermostat scrolls
Check Furnace” message.
EC
Inducer motor
overcurrent
fault.
INDUCER
FAULT OR
INDUCER
LOCKOUT
EC Lingering Inducer motor
overcurrent detected.
Reset system power and verify
inducer is running properly.
Replace inducer or integrated
control module, if necessary.
No furnace operation.
Integrated control module LED
display provides
Ed
error code.
Ed
•Manual reset
rollout switch is
open.
ROLLOUT
OPEN
Ed
Orifice plate out of position.
Blocked heat exchanger.
Burners out of alignment.
Defective heat exchanger.
Line up orifice plate.
Remove Blockage from heat
exchanger.
Line up burners.
Check for flame disturbance on
roll out when blower comes on.
Turn power OFF prior to repair.
No furnace operation.
Integrated control module LED
display provides Ef error code.
EF
Open auxiliary
input.
AUXILIARY
OPEN
EF
Open circuit between aux in or aux
out.
Missing jumper.
Open float switch.
Install jumper.
Inspect float switch.
Turn power OFF prior to repair.
No furnace operation.
Integrated control module LED
display provides
E5
error code.
ComfortNet thermostat displays
Battery Power”.
E5
Open Fuse. Not Displayed Not
Displayed
Short in low voltage wiring Locate and correct short in
low voltage wiring.
Turn power OFF prior to repair.
Replace fuse with 3- amp automotive
type
Normal furnace operation.
Integrated control module LED
display provides
E6
error code.
E6
•Flame sense
micro amp
signal is low.
WEAK
FLAME
E6
Flame sensor is coated/oxidized.
Flame sensor incorrectly
positioned in burner flame.
Lazy burner flame due to improper
gas pressure or combustion air.
Clean flame sensor if coated/oxidized.
Inspect for proper sensor alignment.
Check inlet air piping for blockage,
proper length, elbows, and termination.
Compare current gas pressure to rating
plate. Adjust as needed.
Turn power OFF prior to repair.
Clean flame sensor with steel wool.
See "Vent/Flue Pipe" section for
piping details.
See rating plate for proper gas
pressure.
Furnace fails to operate on high
stage; furnace operates normally
on low stage.
Integrated control module LED
display provides
E8
error code.
E8
High stage
pressure switch
circuit is closed
at start of
heating cycle.
Induced draft
blower is
operating.
Furnace is
operating on
low stage only
PS2
CLOSED
E8
High stage pressure switch
contacts sticking.
Shorts in pressure switch circuit
wiring.
Replace high stage pressure switch.
Repair short in wiring
Turn power OFF prior to repair.
Replace pressure switch with correct
replacement part.
Diagnostic
& Status
LED Codes
Fault
Description
Symptoms of Abnormal Operation
(Non-communicating
& ComfortNet™ Thermostat)
ComfortNet
Thermostat Only
Possible Causes Corrective Actions Notes & Cautions