Submittal Sheet

Product SPecificationS
SS-GMVC95 www.goodmanmfg.com 9
GcVc9 airflow data
Continuous Fan Speeds
Model
Maximum
CFM
Continuous
Fan Speed¹
GMVC950453BX 1400 420
GMVC950704CX 1760 530
GMVC950905CX 2200 660
GMVC950905DX 2200 660
GMVC951155DX 2200 660
GCVC950704CX 1760 530
GCVC950905DX 2200 660
GCVC91155DX 2200 660
¹ Connuous fan speed is 30% of furnace maximum CFM
GCVC91155DX
Cooling Speeds
GCVC91155DX
Heating Speeds (Rise Range: 40 - 70°F)
High Stage Low Stage High Stage Low Stage
Tap Adjust CFM* Tap Adjust CFM* Tap Adjust CFM* Rise Tap Adjust CFM* Rise
A
Minus(-) 705
A
Minus(-) 457
A
Minus(-) 1583 63
A
Minus(-) 1093 63
Normal 783 Normal 508 Normal 1759 56 Normal 1214 56
Plus (+) 861 Plus (+) 559 Plus (+) 1935 51 Plus (+) 1335 51
B
Minus(-) 982
B
Minus(-) 621
B
Minus(-) 1612 61
B
Minus(-) 1106 61
Normal 1091 Normal 690 Normal 1791 55 Normal 1229 55
Plus (+) 1200 Plus (+) 759 Plus (+) 1970 50 Plus (+) 1352 50
C
Minus(-) 1265
C
Minus(-) 815
C
Minus(-) 1654 60
C
Minus(-) 1166 60
Normal 1406 Normal 906 Normal 1838 54 Normal 1296 54
Plus (+) 1547 Plus (+) 997 Plus (+) 2022 49 Plus (+) 1426 49
D
Minus(-) 1628
D
Minus(-) 1049
D
Minus(-) 1690 59
D
Minus(-) 1172 59
Normal 1809 Normal 1165 Normal 1878 53 Normal 1302 53
Plus (+) 1990 Plus (+) 1282 Plus (+) 2066 48 Plus (+) 1432 48
* @ .1" - .5" w.c. ESP
Notes
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
Do not operate above .5” w.c. ESP in heang mode. Operang CFM between .5” and .8” w.c. is tabulated for cooling purposes only.
Gas Altitude Kit Orifice
Manifold Pressure
Pressure Switch
Change
High Stage Low Stage
Natural 0-7000 Changeover None #43 3.5” W.C. 1.9” W.C. None
Propane 0-7000 LPM-03B & LPM-05 #55 10.0: W.C. 6.0” W.C. None
For installaon in Canada, gas furnaces are cered only to 4,500 .
For GCVA installaons above 7,000 ., please refer to your Goodman distributor for required kit(s).
Standard altitude inStallationS