Submittal Sheet

produCt speCifiCatioNs
8 www.goodmanmfg.com SS-GMVC95
gCVC95 airflow data




   
             
A
Minus 594
A
Minus 324
A
Minus 1107 55
A
Minus 783 77
Normal 660 Normal 360 Normal 1230 49 Normal 870 69
Plus 726 Plus 396 Plus 1353 45 Plus 957 63
B
Minus 747
B
Minus 468
B
Minus 1215 50
B
Minus 855 71
Normal 830 Normal 520 Normal 1350 45 Normal 950 64
Plus 913 Plus 572 Plus 1485 41 Plus 1045 58
C
Minus 1017
C
Minus 702
C
Minus 1323 46
C
Minus 936 65
Normal 1130 Normal 780 Normal 1470 41 Normal 1040 58
Plus 1243 Plus 858 Plus 1617 37 Plus 1144 53
D
Minus 1314
D
Minus 864
D
Minus 1440 42
D
Minus 1017 59
Normal 1460 Normal 960 Normal 1600 38 Normal 1130 53
Plus 1606 Plus 1056 Plus 1760 34 Plus 1243 49
* @ .1" - .5" w.c. ESP




   
             
A
Minus 729
A
Minus 504
A
Minus 1458 55
A
Minus 1008 80
Normal 810 Normal 560 Normal 1620 50 Normal 1120 72
Plus 891 Plus 616 Plus 1782 45 Plus 1232 65
B
Minus 999
B
Minus 666
B
Minus 1575 51
B
Minus 1098 73
Normal 1110 Normal 740 Normal 1750 46 Normal 1220 66
Plus 1221 Plus 814 Plus 1925 42 Plus 1342 60
C
Minus 1287
C
Minus 828
C
Minus 1674 48
C
Minus 1152 70
Normal 1430 Normal 920 Normal 1860 43 Normal 1280 63
Plus 1573 Plus 1012 Plus 2046 39 Plus 1408 57
D
Minus 1674
D
Minus 1071
D
Minus 1773 45
D
Minus 1206 67
Normal 1860 Normal 1190 Normal 1970 41 Normal 1340 60
Plus 2046 Plus 1309 Plus 2167 37 Plus 1474 55
* @ .1" - .5" w.c. ESP

All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
Do not operate above .5” w.c. ESP in heang mode. Operang CFM between .5” and .8” w.c. is tabulated for cooling purposes only.