Submittal Sheet

produCt speCifiCatioNs
SS-GMVC95 www.goodmanmfg.com 3
speCifiCatioNs

















High Fire Input¹ 46,000 69,000 92,000 92,000 115,000 69,000 92,000 115,000
High Fire Output¹ 45,000 67,000 90,000 90,000 109,000 65,000 87,000 109,000
Low Fire Input¹ 32,000 48,000 64,000 64,000 80,000 48,000 64,000 80,000
Low Fire Output¹ 30,800 46,400 61,700 61,700 77,400 45,000 60,100 77,400
AFUE² 95 95 95 95 95 95 95 93
Tons AC @ 0.5” ESP 1.5 - 3.0 1.5 - 4.0 2.0 - 5.0 2.0 - 5.0 2.0 - 5.0 1.5 - 4.0 2.0 - 5.0 2.0 - 5.0
Temperature Rise Range (°F) 30 - 60 30 - 60 30 - 60 30 - 60 30 - 60 25-55 25-55 40-70

Size (D x W) 10” x 8” 10” x 10” 11” x 10” 11” x 10” 11” x 10” 10” x 10” 11” x 10” 11” x 10”
Horespower @ 1050 RPM ½ ¾ 1 1 1 ¾ 1 1
Speed Variable Variable
Vent Diameter³ 2” 2” 3” 3” 3” 2” 3” 3”
No. of Burners 2 3 4 4 5 3 4 5
Disposable Filter (in²) 288 384 480 480 486 384 480 486

Min. Circuit Ampacity (amps)
4
11.3 14.1 14.4 14.4 14.4 11.2 15.0 14.4
Max. Overcurrent Protecon
5
15 amps 15 amps 15 amps 15 amps 15 amps 15 amps 15 amps 15 amps
 121 145 160 160 170 139 165 160
¹ Natural Gas BTU/h
² DOE AFUE based upon Isolated Combuson System (ICS)
³ Installer must supply one or two PVC pipes: one for combuson air (oponal) and one for the ue outlet (required). Vent pipe must be either 2” or 3”
in diameter, depending upon furnace input, number of elbows, length of run and installaon (1 or 2 pipes). The oponal Combuson Air Pipe is depen-
dent on installaon/code requirements and must be 2” or 3” diameter PVC.
4
Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined in accordance with Naonal Electrical
Codes. Extensive wire runs will require larger wire sizes.
5
Maximum Overcurrent Protecon Device refers to maximum recommended fuse or circuit breaker size. May use fuses or HACR-type circuit breakers of
the same size as noted.

All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply.
Gas Service Connecon ½” FPT
Important: Size fuses and wires properly and make electrical connecons in accordance with the Naonal Electrical Code and/or all exisng local codes.