GMES8 GCES8 Service Manual

TROUBLESHOOTING
37
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
Circulator blower runs
continuously. No furnace
operation.
• Integrated control
module diagnostic LED
is ashing FOUR (4)
ashes.
Primary limit circuit
is open.
• Check primary limit.
Replace if necessary.
• Check lters and
ductwork for blockage.
Clean lters or remove
obstruction.
• Check circulator blower
speed and performance.
Correct speed or replace
blower if necessary.
• Tighten or correct wiring
connection.
Turn power OFF
prior to repair.
• Replace primary
limit with proper
replacement part.
• Replace blow-
er with correct
replacement part.
4
4 FLASHES
Faulty primary limit switch.
Insufcient conditioned air
over the heat exchanger.
Blocked lters, restrictive
ductwork, improper circula-
tor blower speed, or failed
circulator blower.
Loose or improperly con-
nected wiring.
Fault Description(s)
Possible Causes
Corrective Action
Cautions and
Notes
Symptoms of Abnormal
Operation
Associated
LED Code
2
Normal furnace opera-
tion.
• Integrated control
module diagnostic LED
is ashing SEVEN (7)
ashes.
Flame sense micro-
amp signal is low.
• Clean ame sensor if
coated/oxidized.
• Inspect for proper sensor
alignment.
• Check inlet air piping for
blockage, proper length,
elbows, and termination.
• Compare current gas
pressure to rating plate
info. Adjust as needed.
Turn power OFF
prior to repair.
Clean ame sen-
sor
See “Vent/Flue
Pipe” section for
piping details.
See rating plate
for proper gas
pressure.
7
7 FLASHES
Flame sensor is coated/
oxidized.
Flame sensor incorrectly
positioned in burner ame.
Lazy burner ame due to
improper gas pressure or
combustion air.
Induced draft blower and
circulation blower runs
continuously. No furnace
operation.
• Integrated control
module diagnostic LED
is ashing FIVE (5)
ashes.
Flame sensed with
no call for heat.
Correct short at ame
sensor or in ame
sensor wiring.
Turn power OFF
prior to repair.
5
5 FLASHES
Short to ground in ame
sense circuit.
Circulator blower runs
continuously. No furnace
operation.
Integrated control mod-
ule diagnostic LED is
ashing SIX (6) ashes.
Rollout limit circuit is
open.
• Check burners for proper
alignment.
• Check ue and air inlet
piping for blockage, prop-
er length, elbows, and
termination. Correct as
necessary.
• Check rollout limit. Re-
place if necessary.
• Check induced draft blow-
er for proper performance.
Replace, if necessary.
• Tighten or correct wiring
connection.
Turn power OFF
prior to repair.
See “Vent/Flue
Pipe” section for
piping details.
• Replace rollout
limit with correct
replacement part.
• Replace induced
draft blower with
correct replace-
ment part.
6
6 FLASHES
• Flame rollout.
Misaligned burners, blocked
ue and/or air inlet pipe, or
failed induced draft blower.
Loose or improperly con-
nected wiring.
Faulty rollout limit.
Furnace fails to operate.
Integrated control mod-
ule diagnostic LED is
ashing continuously.
Polarity of 115 or
24 volt power is
reversed.
Review wiring diagram
to correct polarity.
Reverse orange and
gray wires going to
transformer.
Verify proper ground.
Correct if necessary.
Turn power OFF
prior to repair.
C
CONTINUOUS/
RAPID FLASH
Polarity of 115 volt AC pow-
er to furnace or integrated
control module is reversed.
Orange and gray wires to
transformer are reversed.
Poor unit ground.
PCBBF145(S) CONTROL BOARD