GMEC96 Service Manual

TROUBLESHOOTING
46
Symptoms
Green
LED Code
Amber
LED Code
Red
LED Code
Fault Description Check Cautions
Furnace fails to operate
•Control board LED is off
•None •None •None
Defective disconnect switch
defective door switch • No
115 volt power •No 24 volt
power
Determine cause and restore
proper high and low volt power
supply
Confirm electrically safe
condition before
proceeding with repairs
Furnace is waiting for a
call
Solid ON None None
Furnace is not receiving a
call
None Required
Confirm electrically safe
condition before
proceeding with work
Furnace fan only is
running
•Rapid Flash None •None
•Furnace is receiving a call for
fan (24 volts on G terminal
None Required
Confirm electrically safe
condition before
proceeding with work
Normal operation with
low stage call for cooling
(Ylo & G)
•One
repeating
flash
•None None
Normal operation with low
stage call for cooling (Ylo & G)
None Required
Confirm electrically safe
condition before
proceeding with work
Normal operation with
high or single stage call
for cooling (Y & G)
•Two
repeating
flashes
•None None
Normal operation with high
or single stage call for cooling
(Y & G)
None Required
Confirm electrically safe
condition before
proceeding with work
Normal operation with
low stage call for heat
(W1)
•None
•One
repeating
flash
•None
Normal operation with low
stage call for heat (W1)
None Required
Confirm electrically safe
condition before
proceeding with work
Normal operation with
high or single stage call
for heat
•None
•Two
repeating
flashes
•None
Normal operation with high
or single stage call for heat
None Required
Confirm electrically safe
condition before
proceeding with work
Furnace does not
operate, three Amber
flashes on control board
•None
Three
repeating
flashes
•None •W2 call present without W1
•Faulty thermostat or
thermostat wiring or
improperly connected
thermostat wires
Confirm electrically safe
condition before
proceeding with repairs
Furnace does not
operate, four Amber
flashes on control board
•None
•Four
repeating
flashes
•None
•Ylo or Y call present without
G
•Faulty thermostat or
thermostat wiring or
improperly connected
thermostat wires
Confirm electrically safe
condition before
proceeding with repairs
Furnace does not
operate, rapid Amber
flashes on control board
None Rapid None •Low flame sense current
•Dirty / coated flame rod, poor
flame, improper gas pressure,
poor flame sense wire or
connections
Clean flame rod with
steel wool. Confirm
electrically safe condition
before proceeding with
repairs
Furnace does not
operate, one Red flash
on control board
•None •None
•One
repeating
flash
Flame sensed when no
flame should be present
•Gas valve stuck open,
improper wiring to gas valve,
shorted flame rod or wire
•Confirm electrical and
gas safe conditions
before proceeding with
repairs
Furnace does not
operate, two Red
flashes on control board,
possible inducer
operation
•None •None
•Two
repeating
flashes
Pressure switch stuck closed
Faulty pressure switch,
pressure switch wires shorted,
control board inducer relay
stuck closed
Confirm electrically safe
condition before
proceeding with repairs
Furnace does not
operate, three Red
flashes on control board
•None •None
•Three
repeating
flashes
•Low fire pressure switch
stuck open
Faulty pressure switch,
pressure switch or tubing or
wiring / connection, control
board inducer relay failed, vent
pipe restriction / excessive
elbows or length
Confirm electrically safe
condition before
proceeding with repairs