GMEC96 Service Manual

SYSTEM OPERATION
33
DIP SWITCH S ETTINGS
HEATING
DIP SWITCH SETTING
Switch Bank 3
Static
0.1 0. 2 0. 3 0. 4 0. 5 0. 6 0.7 0.8
Switch 1 2 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM CFM CFM
W1
1283 48 1219 51 1162 53 1101 56 1036 59 974 917 864
W2
1811 49 1772 50 1733 51 1690 52 1644 54 1590 1551 1492
W1
1438 43 1366 45 1309 47 1254 49 1163 53 1133 1077 1013
W2
1811 49 1772 50 1733 51 1690 52 1644 54 1590 1551 1492
W1
1438 43 1366 45 1309 47 1254 49 1163 53 1133 1077 1013
W2
1384 64 1324 N/ A 1271 N/ A 1204 N/ A 1145 N/ A 1088 1029 985
W1
1384 44 1324 47 1271 48 1204 51 1145 54 1088 1029 985
W2
2008 44 1963 45 1964 45 1916 46 1876 47 1839 1801 1759
*NOT RECOMMENDED
**Factory Def ault
**OFF OFF
ON OFF
ON ON*
OFF ON
COOLING
DIP SWITCH SETTING 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Switch Bank 2 CFM CFM CFM CFM CFM CFM CFM CFM
Switch 1 2 3
G
1283 1219 1162 1101 1036 974 917 864
Ylo
1438 1366 1309 1254 1163 1133 1077 1013
Y
2008 1963 1964 1916 1876 1839 1801 1759
Ylo
1384 1324 1271 1204 1145 1088 1029 985
Y
2008 1963 1964 1916 1876 1839 1801 1759
Ylo
1384 1324 1271 1204 1145 1088 1029 985
Y
1811 1772 1733 1690 1644 1590 1551 1492
Ylo
1438 1366 1309 1254 1163 1133 1077 1013
Y
2008 1963 1964 1916 1876 1839 1801 1759
Ylo
1811 1772 1733 1690 1644 1590 1551 1492
Y
2008 1963 1964 1916 1876 1839 1801 1759
*MEC961005CN
OFF OFF ON
**OFF OFF OFF
ON ON OFF
OFF ON ON
ON OFF ON