GMEC96 Service Manual

SYSTEM OPERATION
32
DIP SWITCH S ETTINGS
HEATING
DIP SWITCH SETTING
Switch Bank 3
Static
0. 1 0. 2 0. 3 0.4 0.5 0. 6 0. 7 0. 8
Switch 1 2 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM CFM CFM
W1
1522 40 1464 42 1402 44 1338 46 1280 48 1230 1167 1101
W2
1861 47 1803 49 1749 50 1698 52 1653 53 1594 1549 1504
W1
1004 61 890 69 805 N/ A 710 N/ A 620 N/ A 553 474 406
W2
1861 47 1803 49 1749 50 1698 52 1653 53 1594 1549 1504
W1
1004 61 890 69 805 N/ A 710 N/ A 620 N/ A 553 474 406
W2
1312 67 1235 N/ A 1170 N/ A 1101 N/ A 1037 N/ A 962 880 820
W1
1312 47 1235 50 1170 53 1101 56 1037 59 962 880 820
W2
1772 50 1713 51 1662 53 1609 55 1540 57 1498 1452 1399
*NOT RECOMMENDED
**Fact ory Default
**OFF OFF
ON OFF
ON ON*
OFF ON
COOLING
DIP SWITCH SETTING 0.10.20.30.40.50.60.70.8
Switch Bank 2 CFM CFM CFM CFM CFM CFM CFM CFM
Switch 1 2 3
G
1522 1464 1402 1338 1280 1230 1167 1101
Ylo
1004 890 805 710 620 553 474 406
Y
1772 1713 1662 1609 1540 1498 1452 1399
Ylo
1004 890 805 710 620 553 474 406
Y
1312 1235 1170 1101 1037 962 880 820
Ylo
1312 1235 1170 1101 1037 962 880 820
Y
1772 1713 1662 1609 1540 1498 1452 1399
Ylo
1312 1235 1170 1101 1037 962 880 820
Y
1522 1464 1402 1338 1280 1230 1167 1101
Ylo
1312 1235 1170 1101 1037 962 880 820
Y
1861 1803 1749 1698 1653 1594 1549 1504
Ylo
1004 890 805 710 620 553 474 406
Y
1772 1713 1662 1609 1540 1498 1452 1399
*MEC961004CN
**OFF OFF OFF
ON OFF OFF
ON ON OFF
OFF ON OFF
OFF OFF ON
OFF ON ON