GMEC96 Installation Manual

5



with left or right side down. The *CEC96 furnace may be

down. *MEC96 & *CEC96 two-stage gas furnaces features
a multi-speed ECM indoor fan motor, two heating inputs

gas valve. A single stage heating thermostat may also be

the furnace integrated control board.

This furnace is primarily designed for residential home-heating
applications. It is NOT -
bile homes, trailers or recreational vehicles. Neither is it

must be installed indoors (i.e., attic space, crawl space,
or garage area provided the garage area is enclosed with
an operating door).
This furnace can be used in the following non-industrial
commercial applications:


In such applications, the furnace must be installed with the
following stipulations:
It must be installed per the installation instructions
provided and per local and national codes.
It must be installed indoors in a building constructed
on site.
It must be part of a ducted system and not used in a
free air delivery application.
B10259-216
CO can cause serious illness including permanent brain
damage or death.
Advertencia especial para la instalación de calentadores ó manejadoras
de aire en áreas cerradas como estacionamientos ó cuartos de servicio.
B10259-216
El monóxido de carbono puede causar enfermedades severas
como daño cerebral permanente ó muerte.
Las emisiones de monóxido de carbono pueden circular a través
del aparato cuando se opera en cualquier modo.
B10259-216
RISQUE D'EMPOISONNEMENT AU
MONOXYDE DE CARBONE
Le monoxyde de
des
carbone peut causer des maladies graves telles que
dommages permanents au cerveau et meme la mort.
Cette ventilation est nécessaire pour éviter le danger d'intoxication
au CO pouvant survenir si un appareil produisant du monoxyde
de carbone continue de fonctionner au sein de la zone confinée.
It must not be used as a “make-up” air unit.
It must be installed as a two-pipe system for
combustion air.
All other warranty exclusions and restrictions apply

is appropriate for use with natural or propane gas
(If using propane, a propane conversion kit is
required).

optional and the furnace can be vented as a:
Non-direct vent (single pipe) central forced air furnace
in which combustion air is taken from the installation
area or from air ducted from the outside or,
Direct vent (dual pipe) central forced air furnace
in which all combustion air supplied directly to the
furnace burners through a special air intake system
outlined in these instructions.
This furnace may be used as a construction site heater 
if all of the following conditions are met:
The vent system is permanently installed per these
installation instructions.
A room thermostat is used to control the furnace. Fixed
jumpers that provide continuous heating CANNOT be
used and can cause long term equipment damage.

by vibration must not be used
during construction.