GMEC96 Installation Manual
32
If the total external static pressure exceeds the maximum
listed on the furnace rating plate, check for closed damp-
ers, registers, undersized and/or oversized poorly laid out
duct work.
The temperature rise of the furnace must be within the
temperature rise range listed on the furnace rating plate.
Figure 36
Air Cleaner Installation
Location
Maximum
Heating Airflow
Filter (Media)
Dimensions
Part Number
Air Cleaner
Family
Si de or bottom re turn
1200 CFM
16 in X 20 in x 5¼" AM11-1620-5
Si de or bottom re turn 1600 CFM
16 in X 25 in x 5¼" AM11-1625-5
Si de or bottom re turn 1600 CFM
20 in X 20 in x 5¼"
AM11-2020-5
Si de or bottom re turn
2000 CFM 20 in X 25 in x 5¼" AM11-2025-5
Si de return
(for 2 s e pa ra te re turns )
Side return (Right angle) 2000 CFM 20 in X 25 in x 5¼" AM11-2025-5RA
AM11-5RA
Bottom return (platform) 2000 CFM 20 in X 25 in x 5¼"
AM11-2832-5PP
Bottom return (platform) 2000 CFM 20 in X 25 in x 5¼" AM11-2843-5PP
AM11-5PP
AM11-5
2 X 1600 CFM
2, 16 in X 25 in x 5¼"
AM11-3225-5
AM11-3225
AM11-5
Family
AM11-5RA
Family
AM11-5PP
Family