GMEC96 Installation Manual

32
If the total external static pressure exceeds the maximum
listed on the furnace rating plate, check for closed damp-
ers, registers, undersized and/or oversized poorly laid out
duct work.
The temperature rise of the furnace must be within the
temperature rise range listed on the furnace rating plate.


Figure 36
Air Cleaner Installation
Location
Maximum
Heating Airflow
Filter (Media)
Dimensions
Part Number
Air Cleaner
Family
Si de or bottom re turn
1200 CFM
16 in X 20 in x 5¼" AM11-1620-5
Si de or bottom re turn 1600 CFM
16 in X 25 in x 5¼" AM11-1625-5
Si de or bottom re turn 1600 CFM
20 in X 20 in x 5¼"
AM11-2020-5
Si de or bottom re turn
2000 CFM 20 in X 25 in x 5¼" AM11-2025-5
Si de return
(for 2 s e pa ra te re turns )
Side return (Right angle) 2000 CFM 20 in X 25 in x 5¼" AM11-2025-5RA
AM11-5RA
Bottom return (platform) 2000 CFM 20 in X 25 in x 5¼"
AM11-2832-5PP
Bottom return (platform) 2000 CFM 20 in X 25 in x 5¼" AM11-2843-5PP
AM11-5PP
AM11-5
2 X 1600 CFM
2, 16 in X 25 in x 5¼"
AM11-3225-5
AM11-3225
AM11-5
Family
AM11-5RA
Family
AM11-5PP
Family