GM9S96 Service Manual

SERVICING
37
WARNING


A temperature activated manual reset control is mounted to
the manifold assembly on 90% furnaces, as shown in the
following illustrations.
Should read continuous unless heat exchanger temperature
is above limit control setting. If not as above, replace the
control.
*
*
*
* *
*
*
2
FLAME
ROLLOUT
SWITCHES


control opens, the air circulation blower will run continuously.
On single-stage models, the ignition control diagnostic light

an open control board fuse.
To aid in identifying these controls, color-coded labels have
󰀩-
out Limit Charts in furnace Technical Manual for tempera-
ture settings and color codes.
WARNING

1. Remove the burner compartment door to gain access
to the rollout switch(es) mounted to burner bracket.
The servicer should reset the ignition control by opening
and closing the thermostat circuit. Then look for the ignitor
glowing which indicates there is power to the ignition control.
Measure the voltage between each side of the rollout control
and ground while the ignition control tries to power the gas
valve.
2. Measure the voltage between each side of the rollout
control and ground during the ignition attempt. Refer

RED
RESET
BUTTON
COLOR
IDENTIFYING


a. If no voltage is measured on either side of con-
trol it indicates ignition control or wiring to control
problem.
b. If voltage is measured on one side of the control
and not the other it indicates the control is open.
c. If voltage is measured on both sides of the control
the wiring to gas valve or valve is at fault.
3. After check and/or replacement of rollout switch, rein-
stall burner compartment door and verify proper unit
operation.

WARNING


-



1. Remove burner compartment door to gain access to
the induced draft blower motor.
2. Disconnect the motor wire leads from its connection
point at the induced draft motor.
3. Using a ohmmeter, test for continuity between each of
the motor leads.