GM9S96 Service Manual

SYSTEM OPERATION
14
*M9S9 / *C9S9 Direct Vent (2-Pipe) & Non-Direct Vent (1-Pipe)
(6)
Maximum Allowable Length of Vent/Flue Pipe
MODEL
PIPE
SIZE
1 2 3 4 5 6 7 8
2^ 108 105 101 97 93 90 86 82
3 126 120 115 110 105 99 94 89
2 55 50 45 40 35 30 25 20
3 127 120 113 106 99 92 85 78
2 30 25 20 15 10 5 N/A N/A
3 72 65 58 51 44 37 30 23
2 30 25 20 15 10 5 N/A N/A
3 72 65 58 51 44 37 30 23
2 40 35 30 25 20 15 10 5
3 72 65 58 51 44 37 30 23
2 60 55 50 45 40 35 30 25
3 168 161 154 147 140 133 126 119
2 30 25 20 15 10 5 N/A N/A
3 113 106 99 92 85 78 71 64
2 N/A N/A N/A N/A N/A N/A N/ A N/A
3 65 58 51 44 37 30 23 16
MODEL
PIPE
1 2 3 4 5 6 7 8
2^ 7 5 71 67 63 60 56 52 48
3 126 120 115 110 105 99 94 89
2 45 40 35 30 25 20 15 10
3 168 161 154 147 140 133 126 119
2 35 30 25 20 15 10 5 N/A
3 168 161 154 147 140 133 126 119
2 60 55 50 45 40 35 30 25
3 113 106 99 92 85 78 71 64
2 45 40 35 30 25 20 15 10
3 120 113 106 99 92 85 78 71
2 40 35 30 25 20 15 10 5
3 151 144 137 130 123 116 109 102
2 N/A N/A N/A N/A N/A N/A N/ A N/A
3 158 151 144 137 130 123 116 109
2 100 95 90 85 80 75 70 65
3 137 130 123 116 109 102 95 88
2 45 40 35 30 25 20 15 10
3 168 161 154 147 140 133 126 119
2 40 35 30 25 20 15 10 5
3 120 113 106 99 92 85 78 71
2 N/A N/A N/A N/A N/A N/A N/ A N/A
3 113 106 99 92 85 78 71 64
2 N/A N/A N/A N/A N/A N/A N/ A N/A
3 110 103 96 89 82 75 68 61
*M9S920403AN
Number of Elbow s
(3) (5)
*M9S920603BN
*M9S960403AN
*M9S960803BN
*M9S960804BN
*M9S960603BN
*M9S920803BN
*M9S920804CN
*M9S920805CN
*M9S921004CN
*M9S921005CN
*M9S921205DN
*M9S960805CN
*M9S961005CN
*C9S961005CN
*C9S961205DN
*M9S961205DN
*C9S960403BN
*C9S960603BN
*C9S960804CN
1. Maximum allowable limits listed on individual lengths for inlet and

2.            
and one elbow/tee.
3. -
mining the number of elbows in the piping system.
4. 
5. 
elbows should be considered equivalent to one 90 deg. elbow.
6. One 90° elbow should be secured to the combustion air intake
connection.


Refer to the preceding table for applicable length, elbows,
-
bustion air intake pipe systems of a non-direct vent (single
pipe) installation. The number of elbows tabulated rep-
resents the number of elbows and/or tees in each (Vent/Flue
& Combustion Air Intake) pipe. Elbows and/or tees used in
the terminations must be included when determining the
number of elbows in the piping systems.
If the combustion air intake pipe is to be installed above a

will be objectionable, insulation of the combustion air pipe
       


        
roof, or horizontally, as through an outside wall.

 Vent/Flue Pipe and Combustion
Air Pipe - Termination Locations section in this manual or
the installation instructions for details concerning location
restrictions. The penetration of the vent through the roof
          
with a plastic plumbing vent.
 Terminate both pipes in the same pressure zone
(same side of roof, no major obstacles between pipes, etc.).
R
L
I
N
E





9
6
M
AX
-
3
M
I
N
12” MIN
HEIGHT DIFFERENCE
BETWEEN
INTAKE AND VENT
12” MIN TO ROOF OR HIGHEST
ANTICIPATED SNOW LEVEL
STRAIGHT
ELBOWS
   
 Vent/Flue Pipe and Combus-
tion Air Pipe - Termination Locations section in this manual
or the installation instructions for details concerning location


3” diameter pipe. To secure the pipe passing through the
wall and prohibit damage to piping connections, a coupling
should be installed on either side of the wall and solvent
cemented to a length of pipe connecting the two couplings.
The length of pipe should be the wall thickness plus the

outside of the wall. The wall penetration should be sealed
with silicone caulking material.