GM9S80 Installation Manual

16

One of the most common causes of a problem in a forced


     
cause premature heat exchanger failure.
A new home may require more frequent replacement until all
construction dust and dirt is removed.
Upflow Models Minimum Recommended Filter Size
*0403A* 1 - 16 X 25 Side or 1 - 14 X 24 Bottom Return
*0603A* 1 - 16 X 25 Side or 14 X 24 Bottom Return
*0603B* 1 - 16 X 25 Side or Bottom Return
*0604B* 1 - 16 X 25 Side or Bottom Return
*0803B* 1 - 16 X 25 Side or Bottom Return
*0804B* 1 - 16 X 25 Side or Bottom Return
*0804C* 1 - 16 X 25 Side or Bottom Return
*0805C*
1 - 16 X 25 Side or Bottom Return¹
*1005C* 2 - 16 X 25 Side or 1 - 20 X 25 Bottom Return¹
*1205D* 2 - 16 X 25 Side or 1 - 24 X 24 Bottom Retur
Downflow Models
*0403A* 2 - 10 X 20 or 1 - 14 X 25 Top Return
*0603A* 2 - 10 X 20 or 1 - 14 X 25 Top Return
*0804B* 2 - 14 X 20 or 1 - 16 X 25 Top Return
*0805C* 2 - 14 X 20 or 1 - 20 X 25 Top Return
*1005C* 2 - 14 X 20 or 1 - 20 X 25 Top Return
¹ = Use 2 - 16 X 25 filters and two side returns or 20 X 25 filter on
bottom return if furnace is connected to a cooling unit over 4 tons
nominal capacity
Larger filters may be used, filters may also be centrally located
A combination of one side & bottom may be used instead of both sides


 Wiring routing must not interfere with circu-

Low voltage connections can be made through either the
right or left side panel. Thermostat wiring entrance holes

shows connections for a “heat/cool system”.
-
-
agram, located on the blower compartment door, for further


Y
C
Y
C
G
R
W
Y2
Y/Y1
C
G
R
W
ROOM THERMOSTAT
INTEGRATED FURNACE
CONTROL MODULE
REMOTE COOLING UNIT
(SINGLE STAGE)
Thermostat - Single-Stage Heating with Single-Stage Cooling

Y1
C
Y1C
G
R
W
Y2
Y/Y1
C
G
R
W
ROOM THERMOSTAT
INTEGRATED FURNACE
CONTROL MODULE
REMOTE COOLING UNIT
(TWO STAGE)
Y2
Y2
Thermostat - Single-Stage Heating with Two-Stage Cooling


This furnace can be used in conjunction with a heat pump
in a fossil fuel application. A fossil fuel application refers to
a combined gas furnace and heat pump installation which
uses an outdoor temperature sensor to determine the most
󰀩
A heat pump thermostat is required to properly use a sin-
gle-stage furnace in conjunction with a heat pump. Refer to
the fossil fuel kit installation instructions for additional ther-
mostat requirements.
Strictly follow the wiring guidelines in the fossil fuel kit instal-
lation instructions. All furnace connections must be made
to the furnace two-stage integrated control module and the


Two furnaces of the same model may be twinned. The in-
tegrated control board has a 3/16” terminal labeled “TWIN”
located beside the low voltage thermostat connection strip.
Twinning allows simultaneous operation of two furnaces and
forces the indoor blower motors of each furnace to operate
-
       
external kits or parts. The staging and speed tap options
must be set the same on both furnaces.

power supply. The L1 connection to each furnace must be in

service panel phase leg). To verify that the furnaces are in
phase, check from L1 to L1 on each furnace with a voltme-
ter. If the furnaces are in phase, the voltage between both
furnaces will be .