GCVM96 & GMVM96 Technical Information
BLOWER PERFORMANCE SPECIFICATIONS
19
GCVM96 / ACVM96 Low Stage Cooling Speed Charts
Low-Stage Cooling Speeds
Cooling
Speed Tap
Adj ust
Tap
CFM *
Cooling
Speed Tap
Adj ust
Tap
CFM *
Cooling
Speed Tap
Adjust
Ta p
CFM *
Minus(-) 333 Minus(-) 477 Minus(-) 450
Normal 370 Normal 530 Normal 500
Plus (+) 407 Plus (+) 583 Plus (+) 550
Minus(-) 486 Minus(-) 657 Minus(-) 666
Normal 540 Normal 730 Normal 740
Plus (+) 594 Plus (+) 803 Plus (+) 814
Minus(-) 711 Minus(-) 837 Minus(-) 828
Normal 790 Normal 930 Normal 920
Plus (+) 869 Plus (+) 1023 Plus (+) 1012
Minus(-) 882 Minus(-) 1098 Minus(-) 1044
Normal 980 Normal 1220 Normal 1160
Plus (+) 1078 Plus (+) 1342 Plus (+) 1276
* @ .1" - .8" w.c. ESP
Notes:
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
Do not operate above .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for cooling purposes only.
D
GCVM961005DX
Low-Stage Cooling
A
B
C
B
AA
GCVM960805DX
ACVM960805DX
B
DD
CC
GCVM960604CX
ACVM960604CX