GCVC96 Spec Sheet 2019
4 www.goodmanmfg.com SS-GCVC96
SS-GCVC96 www.goodmanmfg.com 5
Airflow Data
MODEL/TEMP RISE RANGE
(MID RISE)
GCVC960403BNB*
35-65 (50)
GCVC960603BNB*
20-50 (35)
GCVC960804CNB*
25-55 (40)
GCVC961005CNB*
35-65 (50)
G C V C 9 6 1 2 0 5 D N B *
35-65 (50)
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
Recommended cfm for high heat /
expected temperature rise
710 50 1400 38 1760 40 1770 50 2150 50
Lowest recommended cfm for hi heat /
expected temperature rise
548 65 1072 50 1290 55 1360 65 1650 65
Maximum cfm for hi heat / expected
temperature rise
1010 35 1400 38 1760 40 2200 40 2200 48
NOTE: Low Heat CFM = High Heat CFM X .7. Low Heat Temperature Rise Is Expected to Equal High Heat Temparatue Rise ± 5% 0140F02402-A
GCVC960403BNB*
Cooling Speed
( @ .1” - .8” w.c. ESP)
GCVC960603BNB*
Cooling Speed
( @ .1” - .8” w.c. ESP)
Tons High-Stage
Low-Stage
CFM
Tons High-Stage
Low-Stage
CFM
1.5 600 420 1.5 600 420
2 800 560 2 800 560
2.5 1,000 700 2.5 1,000 700
3 1,200 840 3 1,200 840
MAX 1,400 MAX 1,400
GCVC960804CNB*
Cooling Speed
( @ .1” - .8” w.c. ESP)
GCVC961005CNB*
Cooling Speed
( @ .1” - .8” w.c. ESP)
Tons High-Stage
Low-Stage
CFM
Tons High-Stage
Low-Stage
CFM
2 800 560 2 800 560
2.5 1,000 700 3 1,200 840
3 1,200 840 4 1,600 1,120
4 1,600 1120 5 2,000 1,400
MAX 1,760 MAX 2,200
GCVC961205DNB*
Cooling Speed
( @ .1” - .8” w.c. ESP)
Tons High-Stage
Low-Stage
CFM
2 800 560
3 1,200 840
4 1,600 1,120
5 2,000 1,400
MAX 2,200
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
Do not operate above .5” w.c. ESP in heang mode. Operang CFM between .5” and .8” w.c. is tabulated for cooling purposes only.