GMVC9 GCVC9 Installation Instructions
39
NOTE: To enable adjustments and select -5, 5, -10 or 10% trim, you must set dip switch S5-2 to ON. If S5-2 is in the OFF
position, you will receive 0% trim.
7. Select the heating speed for your model from the heating speed chart in the Specification Sheet. The adjust
setting (already esthe cooling speed selection) determines which set of speeds are available. The selected speed
must provide a temperature rise within the rise range listed with the particular model.
Model Tap
Low
Stage
Cool
High
Stage
Cool
Low
Stage
Heat
High
Stage
Heat
A
403 596 731 990
B 527 796 800 1085
C 675 974 850 1185
D 803 1192 911 1279
A 398 599 667 953
B
557 817 740 1059
C
696 1007 808 1158
D 810 1212 881 1260
A 403 629 855 1202
B 540 806 923 1316
C
705 1023 1033 1389
D
819 1230 1063 1396
A 513 789 867 1228
B 660 967 939 1337
C 791 1182 1016 1430
D 913 1375 1077 1516
A
564 820 1256 1818
B 784 1133 1292 1870
C 982 1464 1316 1910
D 1259 1736 1358 1957
A 547 867 1329 1891
B
831 1160 1362 1940
C
1020 1467 1390 1968
D 1278 1910 1440 2028
A 449 655 682 957
B 569 807 750 1059
C
716 998 820 1155
D
854 1207 888 1251
A 433 656 687 938
B 541 790 751 950
C 686 972 814 986
D
806 1195 874 992
A
556 837 889 1234
B 714 1022 944 1325
C 838 1206 1019 1442
D 991 1475 1068 1528
A 524 784 1209 1759
B
744 1078 1249 1797
C
927 1388 1277 1840
D 1185 1766 1300 1881
A 540 854 1284 1744
B 870 1123 1310 1827
C
1000 1399 1350 1860
D
1235 1804 1388 1918
*MVC960403BN**
*MVC960603BN**
*MVC960803BN**
*MVC960804CN**
*MVC961005CN**
*MVC961205DN**
Airflow Table
*CVC960403BN**
*CVC960603BN**
*CVC960804CN**
*CVC961005CN**
*CVC961205DN**
OFF
OFF
• ramps up to 50% of the demand for 1/2 minute, then ramps to 85% of the full
cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor
then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
Profile D
Figure 53
12
AOFFOFF
BONOFF
COFFON
D* ON ON
Switch Bank: S3
Cooling Speed
Taps
DIP Sw itch No.
(*Indicates factory setting)
34
+ 5%* OFF OFF
- 5% ON OFF
+ 10% OFF ON
- 10% ON ON
Switch Bank: S3
Adjust Taps
DIP Sw itch No.
(*Indicates factory setting)