Installation Manual

34



Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
1 400
2.3 920 3.6 1440 4.9 1960
1.1 440 2.4 960 3.7 1480 5 2000
1.2 480 2.5 1000 3.8 1520 5.1 2040
1.3 520 2.6 1040 3.9 1560 5.2 2080
1.4 560 2.7 1080 4 1600 5.3 2120
1.5 600 2.8 1120 4.1 1640 5.4 2160
1.6 640 2.9 1160 4.2 1680 5.5 2200
1.7 680
3 1200 4.3 1720 5.6 2240
1.8 720 3.1 1240 4.4 1760 5.7 2280
1.9 760 3.2 1280 4.5 1800 5.8 2320
2 800 3.3 1320 4.6 1840 5.9 2360
2.1 840 3.4 1360 4.7 1880 6 2400
2.2 880 3.5 1400 4.8 1920





5. Use the  HVAC phone application to
congure/test  operations.




a. Two-stage outdoor units:
a.Provide a second stage cooling call from the
thermostat and charge accordingly.
b. Single-stage outdoor units:
a.Provide a cooling call from the thermostat and
charge accordingly.

a. Two stage operation using the 
HVAC application:
a. Select the gas heat icon after entering the
furnace menus.
b. Select any value less than 50% for low stage
operation and any value greater than 50% for
high stage operation.
3. Select the Non-Comm Outdoor Setting menu (OdS)
using the on board push buttons or the 
HVAC phone application. Select 1 AC for single stage
Air Conditioners, 1HP for single stage heat pumps,
2 AC for two stage air conditioners and 2 HP for two
stage Heat Pumps.
4. Go to the tonnage units menu (ton) and select the
tonnage value that corresponds to the desired airow
for the outdoor unit. See the following table.