Submittal Sheet
Product SPecificationS
2 www.goodmanmfg.com SS-GMSS96
SS-GMSS96 www.goodmanmfg.com 3
SpeCiFiCationS - GMSS96
GMSS96
0402BNA
GMSS96
0603BNA
GMSS96
0803BNA
GMSS96
0804CNA
GMSS96
0805CNA
GMSS96
1005CNA
GMSS96
1205DNA
High Fire Input¹ 40,000 60,000 80,000 80,000 80,000 100,000 120,000
High Fire Output¹ 38,400 57,600 76,800 76,800 76,800 96,000 115,200
AFUE² 96 96 96 96 96 96 96
Temperature Rise Range (°F) 25 - 55 35 - 65 35 - 65 25 - 55 25 - 55 30 - 60 35 - 65
Vent Diameter³ 2" - 3" 2" - 3" 2" - 3" 2" - 3" 2" - 3" 2" - 3" 3"
No. of Burners 2 3 4 4 4 5 6
Available AC @ 0.5" ESP 1.5 - 3 1.5 - 3 1.5 - 3 1.5 - 4 3 - 5 3 - 5 3 - 5
Size (D x W) 10" x 8" 10" x 8" 10" x 8" 10" x 10" 11" x 10" 11" x 10" 11" x 11"
Horsepower @ 1075 RPM
½ ½ ¾ ¾ ¾
Speed 4 4 4 4 4 4 4
Permanent 341 512 975 683 853 853 1,024
Disposable 171 256 488 341 427 427 512
Min. Circuit Ampacity 9.6 9.6 12.8 11.7 13.7 13.7 13.7
15 15 15 15 15 15 15
111 114 116 139 140 142 154
¹ Natural Gas BTU/h
Vent pipe must be either 2" or 3" in diameter, depending upon furnace input, number of elbows, length of run
and must be 2" or 3" diameter PVC.
• All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply.
• " FPT
•
•
and noise issues.
•
over clearances from the enclosure where accessibility clearances are greater.