Service Manual

TROUBLESHOOTING
43
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
Circulator blower runs
continuously. No
furnace operation.
Integrated control
module diagnostic LED
is flashing FOUR (4)
flashes.
Primary or auxiliary
limit circuit is open.
Check primary/auxiliary
limit. Replace if
necessary.
Check filters and
ductwork for blockage.
Clean filters or remove
obstruction.
Check circulator blower
speed and perfor-
mance. Correct speed
or replace blower if
necessary.
Tighten or correct wiring
connection.
Turn power OFF
prior to repair.
Replace primary/
auxiliary limit with
proper replace-
ment part.
Replace blower
with correct
replacement part.
Faulty primary or auxiliary
limit switch.
Insufficient conditioned air
over the heat exchanger.
Blocked filters, restrictive
ductwork, improper
circulator blower speed, or
failed circulator blower.
Loose or improperly
connected wiring.
Fault Description(s)
Possible Causes
Corrective Action
Cautions and
Notes
Symptoms of Abnormal
Operation
Associated
LED Code
2
Normal furnace
operation.
Integrated control
module diagnostic LED
is flashing SEVEN (7)
flashes.
Flame sense
microamp signal is
low.
Sand flame sensor if
coated/oxidized.
Inspect for proper
sensor alignment.
Check inlet air piping
for blockage, proper
length, elbows, and
termination.
Compare current gas
pressure to rating plate
info. Adjust as needed.
Turn power OFF
prior to repair.
Sand flame sensor
with emery clot.
See “Vent/Flue
Pipe” section for
piping details.
See rating plate for
proper gas
pressure.
7
Flame sensor is coated/
oxidized.
Flame sensor incorrectly
positioned in burner flame.
Lazy burner flame due to
improper gas pressure or
combustion air.
Induced draft blower and
circulation blower runs
continuously. No
furnace operation.
Integrated control
module diagnostic LED
is flashing FIVE (5)
Flame sensed with
no call for heat.
Correct short at flame
sensor or in flame
sensor wiring.
Turn power OFF
prior to repair.
5
Short to ground in flame
sense circuit.
Circulator blower runs
continuously. No
furnace operation.
Integrated control
module diagnostic LED
is flashing SIX (6)
flashes.
Rollout limit circuit
is open.
Check burners for
proper alignment.
Check flue and air inlet
piping for blockage,
proper length, elbows,
and termination.
Correct as necessary.
Check rollout limit.
Replace if necessary.
Check induced draft
blower for proper
performance. Replace,
if necessary.
Tighten or correct wiring
connection.
Turn power OFF
prior to repair.
See “Vent/Flue
Pipe” section for
piping details.
Replace rollout
limit with correct
replacement part.
• Replace induced
draft blower with
correct replace-
ment part.
6
Flame rollout.
Misaligned burners,
blocked flue and/or air inlet
pipe, or failed induced draft
blower.
Loose or improperly
connected wiring.
Faulty rollout limit.
Furnace fails to operate.
Integrated control
module diagnostic LED
is flashing continu-
ously.
Polarity of 115 or 24
volt power is
reversed.
Review wiring diagram
to correct polarity.
Reverse orange and
gray wires going to
transformer.
Verify proper ground.
Correct if necessary.
Turn power OFF
prior to repair.
C
CONTINUOUS/
RAPID FLASH
Polarity of 115 volt AC
power to furnace or
integrated control module is
reversed.
Orange and gray wires to
transformer are reversed.
Poor unit ground.