GCES80 Installation Manual
7
Side
• Adequate combustion/ventilation air must be supplied
to the closet.
• Furnace must be completely sealed to floor or
base. Combustion/ ventilation air supply pipes must
terminate 12” from top of closet and 12” from oor
of closet. DO NOT remove solid base plate for side
return.
• Return air ducts must be completely sealed to
the furnace and terminate outside the enclosure
surfaces.
Clearance in accordance with local installation codes, the
requirements of the gas supplier and the manufacturer’s
installation instructions.
Dיgaugement conforme aux codes d’installation locaux, aux
exigences du fournisseur de gaz et aux instructions
d’installation du fabricant.
Unobstructed front clearance of 24” is recom-
mended.
TOP
B1-VENT SINGLE
(PLENUM)
1" 6" 1" 3" 0" 1"
VENT
SIDES
FRONT
BACK
An upow furnace may be installed in an upright position or
horizontal on either the left or right side panel. Do not install
this furnace on its back. For vertically installed upow furnac-
es, return air ductwork may be attached to the side panel(s)
and/or basepan. For horizontally installed upow furnaces,
return air ductwork must be attached to the basepan. For
counterow furnaces, return ductwork must be attached to
the top end of the blower compartment.
NOTE: Ductwork must never be attached to the back of the
furnace.
For vertical (upow or downow) applications, the
minimum cooling coil width shall not be less than
furnace width minus 1”. Additionally, a coil installed
above an upow furnace or under a counterow
furnace may be the same width as the furnace or may
be one size larger than the furnace. Example: a “C”
width coil may be installed with a “B” width furnace.
For upow applications, the front of the coil and
furnace must face the same direction.
• If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches (457 mm)
above the oor. Protect the furnace from physical
damage by vehicles.
• If the furnace is installed horizontally, the furnace
access doors must be vertical so that the burners re
horizontally into the heat exchanger. Do not install the
unit with the access doors on the “up/top” or “down/
bottom” side of the furnace.
• Do not connect this furnace to a chimney ue that
serves a separate appliance designed to burn solid
fuel.
• For counterow installations, the air conditioning coil
must be downstream from the heat exchanger of the
furnace.
• Counterow installation over a noncombustible oor.
Before setting the furnace over the plenum opening,
ensure the surface around the opening is smooth and
level. A tight seal should be made between the furnace
base and oor by using a silicon rubber caulking
compound or cement grout.
• Counterow installation over a combustible oor.
If installation over a combustible floor becomes
necessary, use an accessory subbase (see
Specication Sheet applicable to your model for
details). A special accessory subbase must be used
for upright counterow unit installations over any
combustible material including wood. Follow the
instructions with the subbase for proper installations.
Do not install the furnace directly on carpeting, tile, or
other combustible material other than wood ooring.
(NOTE: The subbase will not be required if an air
conditioning coil is installed between the supply air
opening on the furnace and the oor.