GC9C96 Installation Manual
33
-
pressure gauge) at either the gas valve inlet pressure
Inlet Gas Supply Pressure
TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE GAS
MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UIT RATING PLATE.
ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS
VALVE PRESSURE REGULATOR.
test screw (inlet/outlet pressure tap) out one turn
Manifold Gas
Pressure
ManifoldGasPressureChart
Gas Range Nominal
Natural 3.2 - 3.8" w.c. 3.5" w.c.
Propane 9.7 - 10.3" w.c. 10.0" w.c.
Manifold Gas Pressure
clockwise to increase pressure or counterclockwise to
clockwise to increase pressure or counterclockwise to
test screw in to seal pressure port (clockwise, 7 in-lb